1. INTRODUCTION
The FX
-2DA type analog output block (hereafter referred to as the FX
2N
digital value of 12 bits into an analog output of two points (voltage and current output), and to forward the
values to the Programmable Controller (hereafter referred to as a PLC).
FX
-2DA can connected to the FX
2N
Programmable Controllers.
1) The analog output is selected from the voltage or current output by the method of connecting wires.
At this time, assume setting to be two channels common analog output.
2) The two analog output channels can accept outputs of 0 to 10V DC, 0 to 5V DC, or 4 to 20mA.
(A mixture of voltage/current output is possible.)
3) Resolution is 2.5mV (0 to 10V DC) and 4µA(4 to 20mA).
4) The digital to analog conversion characteristics can be adjusted.
5) The block occupies 8 I/O points which can be allocated from either the inputs or outputs.
6) The data transfer with the PLC uses the FROM/TO instructions.
FX
/FX
series PLC can use direct specification of buffer memory.
3U
3UC
2. EXTERNAL DIMENSIONS AND PARTS
Mass (Weight): Approx. 0.2kg (0.44lbs)
Accessories: Special Function block number label
3. WIRING
PLC
Extension
cable
*1 Connect a 0.1 to 0.47 µF 25V DC capacitor respective to position *1 when there is voltage
ripple in the voltage output or there is a lot of noise.
*2 For voltage output please short circuit IOUT and COM as shown in the diagram.
*3 Channel number enter
4. CONNECTION WITH PROGRAMMABLE CONTROLLER
1) The FX
-2DA and main unit are connected by a cable on the right of the main unit.
2N
2) Up to 4 FX
-2DA units can connect to the FX
2N
FX
/FX
/FX
3GC
3U
3UC
However the following limitation exists when the undermentioned special function blocks are connected.
FX
:
Main unit and powered extension units of 32 points I/O or less. Consumption current available
2N
for undermentioned special function blocks ≤ 190mA
FX
:
Main unit and powered extension units of I/O 48 points or more. Consumption current available
2N
for undermentioned special function blocks ≤ 300mA
FX
:
Up to 4 undermentioned special function blocks can be connected regardless of the system I/O.
2NC
FX
: Main unit and powered extension units. Up to 2 undermentioned special function blocks can be
0N/1N
connected regardless of the system I/O.
Consumption current of 24V DC for one unit
The consumption of the above units is to be subtracted from the service power supply of the host
PLC.
3) The blocks occupies 8 I/O points (the 8 points can be allocated from either inputs or outputs).
4) FX
-2DA consumes 5V DC 30mA.
2N
The total 5V consumption of all special function blocks connected to either a main unit or an
extension unit must not exceed the 5V source capacity of the system.
, FX
0N
1N
+15V
DC/DC
converter
-15V
FX
-2DA
2N
.
or, up to 4 for the FX
2NC
, FX
, FX
, FX
2N
2NC
3G
VOUT
IOUT
COM
AG
VOUT
IOUT
COM
series PLC, up to 5 for FX
0N
series PLC, all with powered extension units.
FX
-2DA
2N
85mA
-2DA) is used to convert a
2N
, FX
, FX
, and the FX
3GC
3U
Dimensions: mm (inches)
Voltage output
*1
*2
Current output
*3
up to 8 for FX
1N,
FX
-2AD
2N
50mA
series
3UC
Inverter
etc
Recorder
etc
/FX
/
2N
3G
FX
-3A
0N
90mA