Heating Request With Gas Shut Off; Control Board Diagnostic Codes; Control Board - Arcoaire N9MP1 Installation Instruction

90+ single stage gas furnace direct or non--direct vent fan assisted category iv furnace
Table of Contents

Advertisement

Heating Request with Gas Shut Off:

24 VAC signal applied to W terminal of FCB.
The FCB will attempt 4 cycles for ignition then go to soft lockout for 3 hours then try for ignition again as long as the heat call remains.
Power reset will clear lockout.
Inducer motor turns on
Following a 15 second prepurge delay, the igniter begins warm up.
The igniter glows red--hot for 22 seconds, then turns off. The FCB flashes error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FCB continues flashing error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FCB continues flashing error code 6.
The igniter stays off for 17 seconds, then begins to warm up again.
The igniter glows red hot for 22 seconds then turns off. The FCB proceeds to soft lockout and stops flashing error code 6 and begins
flashing error code 6 + 1.
The inducer motor de--energizes after a 15 second post purge.
Control Board Diagnostic Codes (See Figure 54)
OFF
= 24VAC or 115VAC is off, fuse is open
Heartbeat
= Normal operation or no previous Diagnostic Code
ON SOLID
= Soft Lockout -- Furnace Control Error (1 hr delay)
If code repeats immediately following power reset then replace control
1 Flash
= Not used
2 Flashes
= Pressure switch(es) closed when should be open
3 Flashes
= Pressure switch open when should be closed
4 Flashes
= Limit or roll--out switch open (less than 2 minutes)
5 Flashes
= Flame sensed out of sequence
6 Flashes
= Failure to ignite or flame sense lost while running
6 + 1 Flashes = Soft Lockout -- Max trials for ignition reached (3 hr delay)
7 Flashes
= Soft Lockout -- Limit or roll--out switch open longer than 2 minutes (1 hr delay)
(roll--out switch requires manual reset)
8 Flashes
= Permanent Lockout -- Gas valve relay contact stuck closed or miswired gas valve (power reset only)
10 Flashes
= Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions
* If status code recall is needed, briefly (2--3 seconds) remove then reconnect one limit switch wire (main or rollout) to display last stored
status code. Do not remove power or blower door before initiating status code recall or code will be lost. Code is automatically cleared
after 72 hours or upon power reset.
* Proper flame sense microamps: 0.7 microamps D.C. minimum, 2.0 -- 4.0 microamps nominal
Figure 54

Control Board

Blower Off
Delay Jumper
24 VAC
HUM
FUSE
46
Diagnostic Light
115 VAC
HUM
25--24--98
Specifications are subject to change without notice
440 01 1024 01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

N9mpdN9mp2T9mpdH9mpdC9mpd

Table of Contents