Arcoaire N9MP1 Installation Instruction

90+ single stage gas furnace direct or non--direct vent fan assisted category iv furnace
Table of Contents

Advertisement

90+ SINGLE STAGE GAS FURNACE
DIRECT OR NON- -DIRECT VENT FAN ASSISTED
N9MP1/N9MP2/N9MPD/*9MPD
Upflow/Downflow/Horizontal
Recognize safety information. This is the safety--alert symbol
the potential for personal injury.
Understand the signal words DANGER, WARNING, or CAUTION. These words are used with the safety--alert symbol. DANGER identifies the
most serious hazards, those that will result in severe personal injury or death. WARNING signifies a hazard that could result in personal injury or
death. CAUTION is used to identify unsafe practices that could result in minor personal injury or product and property damage. Note is used to
highlight suggestions that will result in enhanced installation, reliability, or operation.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should
install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be
performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached
to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the current edition National Fuel Gas Code (NFGC) ANSI
Z223.1--2006/NFPA No. 54--2006. In Canada, refer to the current edition of the National Standard of Canada Natural Gas and Propane Installation
Code (NSCNGPIC) CSA B149.1--05. Wear safety glasses and work gloves. Have fire extinguisher available during start--up and adjustment
procedures and service calls.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions
exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require
these instructions as a minimum for a safe installation.
International Comfort Products, LLC
Lewisburg, TN 37091 U.S.A.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Combustion & Ventilation Air
4. Vent & Combustion Air Piping
!
could result in personal injury,
and/or death.
Turn Off All Power Before
Servicing.
Portions of the text and tables are reprinted from NFPA 54 / ANSI Z223.1--2006©, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Associa-
tion, Washington, DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in
its entirety.
Printed in U.S.A.
Category IV Furnace

SAFETY REQUIREMENTS

Table of Contents

. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
Specifications are subject to change without notice
!
. When you see this symbol on the furnace and in instructions manuals be alert to
INSTALLER: Affix these instructions
on or adjacent to the furnace.
CONSUMER: Retain these
instructions for future reference.
4
5
9
13
30
11. Sequence of Operation & Diagnostics
33
Technical Support
!
CARBON MONOXIDE POISONING AND FIRE
HAZARD.
Failure to follow safety warnings could result
in personal injury, death, and/or property dam-
age.
This furnace is not designed for use in mobile
homes, trailers or recreational vehicles.
* Denotes Brands (C, H, T)
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARNING
440 01 1024 01
38
39
42
44
45
47
July 2007

Advertisement

Table of Contents
loading

Summary of Contents for Arcoaire N9MP1

  • Page 1 90+ SINGLE STAGE GAS FURNACE DIRECT OR NON- -DIRECT VENT FAN ASSISTED Category IV Furnace N9MP1/N9MP2/N9MPD/*9MPD Upflow/Downflow/Horizontal * Denotes Brands (C, H, T) SAFETY REQUIREMENTS Recognize safety information. This is the safety--alert symbol . When you see this symbol on the furnace and in instructions manuals be alert to the potential for personal injury.
  • Page 2 Required Notice for Massachusetts Installations Important The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA- -54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: INSTALLATION OF CARBON MONOXIDE DETECTORS.
  • Page 3 START- -UP CHECK SHEET For 90+ Furnace (This sheet is optional. Keep this page for future reference.) Date of Start--Up: Calculated Firing Rate:(See Checks and Adjustments Section). Dealer Name: Heating Check Address: Measured Line Pressure when Firing Unit: City, State(Province), Zip or Postal Code: Measured Manifold Gas Pressure: Phone: Temperature of Supply Air:...
  • Page 4: Safe Installation Requirements

    1. Safe Installation Requirements WARNING • This furnace is not to be used for temporary heating of buildings or structures under construction. • This furnace is NOT approved for installation in FIRE, EXPLOSION, AND ASPHYXIATION HAZARD. mobile homes, trailers or recreation vehicles. Improper adjustment, alteration,...
  • Page 5: Location And Clearances

    Frozen Water Pipe Hazard Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes CAUTION from freezing. Instruct them on a service agency to call to provide service, if required. WATER DAMAGE TO PROPERTY HAZARD. --or-- Failure to follow this caution may result in property Install a reliable remote sensing device that will notify...
  • Page 6: Installation Requirements

    Install the vent pipes as short as practical. (See Gas Vent Installation section). Figure 2 Typical Downflow Installation Do NOT install furnace directly on carpeting, tile or other See Vent Termination combustible material other than wood flooring. Coupling on inside Shielding in Vent Section.
  • Page 7 Figure 3 Dimensions & Clearances MINIMUM CLEARANCES TO AIR INTAKE COMBUSTIBLE MATERIALS FOR ALL UNITS VENT (N9MPD & *9MPD) REAR FRONT (combustion air openings in 3″ furnace and in structure) Required For Service 24″ ALL SIDES Of SUPPLY PLENUM 1″ SIDES VENT LEFT SIDE...
  • Page 8: Installation Positions

    Knock Outs and downflow installations or top to bottom for horizontal installations. CAUTION Vent and Combustion Air Connections CUT HAZARD. For venting information literature, call 931.270.4100 with the complete model and serial number of the furnace. Failure to follow this caution may result in personal injury.
  • Page 9: Outdoor Combustion Air Method

    If the furnace is to be installed in a crawl space, consult local The horizontal furnaces may be installed directly on combustible codes. A suitable concrete pad or blocks are recommended for wood flooring or supports as long as all required furnace crawl space installation on the ground.
  • Page 10 Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.) Figure 6 This installation NOT approved in Canada Gas Vent Gable Vent Gas Vent Ventilated Attic Top Above Insulation Gable Vent alternate Inlet Air (1) Gas Vent Outlet Air (2) Ventilated Attic...
  • Page 11 Indoor Combustion Air Standard and Known- Air- Infiltration Rate Methods © NFPA & AGA Indoor air is permitted for combustion and ventilation, if the WARNING Standard or Known- -Air- -Infiltration Rate Method is used. The Standard Method may be used, if the space has no less CARBON MONOXIDE POISONING HAZARD.
  • Page 12 WARNING Ventilation Air Some provincial codes and local municipalities require ventilation CARBON MONOXIDE POISONING HAZARD. or make--up air be brought into the conditioned space as replacement air. Whichever method is used, the mixed return air Failure to follow the steps outlined below for each temperature across the heat exchanger MUST not fall below 60°...
  • Page 13: Contaminated Combustion Air

    Masonry acid washing materials. and ventilation air. Vent and Combustion Air Piping Guidelines Single Pipe (N9MP1 Models) This furnace is approved for venting with Schedule 40 PVC, CPVC, ABS fittings, and Cellular Core and SDR--26 PVC pipe. This furnace is certified as a category IV appliance. This furnace...
  • Page 14 Figure 35 in this manual. 45° elbows can be substituted for one 90° elbow. The elbow or For Single Pipe Installation, models N9MP1, N9MPD or elbows used for vent termination outside the structure ARE *9MPD, refer to Figure 9 for vent termination clearances.
  • Page 15 Direct Vent Termination Clearance Figure 8 25--24--65--2 AREA WHERE TERMINAL IS NOT PERMITED VENT TERMINAL AIR SUPPLY INLET Item Clearance Description Canadian Installation (1) U.S. Installation (2) Clearance above grade, veranda, porch, deck, balcony, or 12″ (30cm) # 12″ (30 cm) anticipated snow level Clearance to a window or door that may be opened 6″...
  • Page 16 Other than Direct Vent Termination Clearance Figure 9 25--24--65--2 AIR SUPPLY INLET VENT TERMINAL AREA WHERE TERMINAL IS NOT PERMITED Item Clearance Descriptions Canadian Installation (1) U.S. Installation (2) Clearance above grade, veranda, porch, deck, balcony, or 12″ (30cm) # 12″...
  • Page 17 Condensate Drain Trap DO NOT trap the drain line in any other location than at the condensate drain trap supplied with the furnace. This furnace removes both sensible and latent heat from the CAUTION products of combustion. Removal of the latent heat results in condensation of the water vapor.
  • Page 18 Figure 11 Upflow Installations Top Vent On Some Models ONLY Single Pressure Switch Plastic Caps (2) Yellow or black Coupling & Clamps (Optional) Vent Drain & Clamps Dual Pressure Switch Detail Drain Tee Relief Tube Black Rubber ″ ID Drain Tube Black Rubber ″...
  • Page 19 • A standard field supplied 2″ PVC tee (N9MP1 models), or Connect the tee trap and the main drain line exiting the casing as • A 2″ PVC coupling fastened onto the drain tee (N9MPD and shown in Figure 20.
  • Page 20 Figure 13 All Models Vent through Right- -Side Plastic Cap Yellow or black On Some Models ONLY Relief Tube Either: The PVC Black Rubber Drain Tee or a field Dual ″ ID Vent Drain supplied 2″ PVC Tee Pressure Switch &...
  • Page 21 A standard field supplied 2″ PVC tee (N9MP1), or • secure with screws.
  • Page 22 Using cover plate and gasket provided in the loose parts bag, cover the A standard field supplied 2″ PVC tee (N9MP1 models), or • hole from the burner compartment to the blower compartment and A 2″...
  • Page 23 Cut an appropriate length of 2″ PVC pipe, long enough to exit the cabinet and connect the vent drain to either: Remove knockout from the side of the furnace casing where drain A standard field supplied 2″ PVC tee (N9MP1 models), or tube will exit. •...
  • Page 24 Disconnect the hoses from the trap assembly, and remove trap either: and trap mounting bracket from the blower compartment. Using A standard field supplied 2″ PVC tee (N9MP1 models), or • cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and A 2″...
  • Page 25 Figure 18 Horizontal Right through Top Single Pressure Switch Detail Trap Connection “Clamp ears” Alternate Orienta- Pointed OUT tion Plastic Cap AIRFLOW Yellow or black Coupling & Clamps Preassemble & (Optional) insert into furnace Field WARNING Supplied Tee Vent Drain &...
  • Page 26 A standard field supplied 2″ PVC tee (N9MP1 models), or • Remove knockout from the side of the furnace casing where drain A 2″ PVC coupling fastened onto the drain tee (N9MPD and •...
  • Page 27 Important: Prime both traps with water before operation. Connecting Tee Trap to Condensate Figure 20 Failure to prime the traps may result in discharge of flue gases Trap and Main Drain Line from the condensate drain line and open tee for a period of time, and may result in temporary lockout of the furnace upon start up.
  • Page 28: Joining Pipe And Fittings

    After checking pipe and socket for proper fit, wipe socket Proper Sealing Procedure for and pipe with cleaner-primer. Apply a liberal coat of primer Figure 21 Combustion Blower to inside surface of socket and outside of pipe. Do NOT allow primer to dry before applying cement. Vent Pipe Apply a thin coat of cement evenly in the socket.
  • Page 29 Extend vent pipe and combustion air pipe through the wall Rooftop Termination ″ to 1″ and seal area between pipe and wall. Figure 24 Install the couplings, nipple and termination elbows as shown and maintain spacing between vent and combustion air piping as indicated in Figure 22 and Figure 23.
  • Page 30: Concentric Termination

    Concentric Vent and Combustion- - Rooftop Inlet Vent and Exhaust- - Figure 26 Figure 29 Air Sidewall Termination Air Termination 18″ Min. for Cold Climates (Sustained temperatures 0° F and below for 24 or 8″ Min. more consecutive hours) Inlet 20′...
  • Page 31: Concentric Vent Termination

    Do NOT terminate over public walkways. Avoid areas where condensate may cause problems such as above Concentric Vent Roof Installation Figure 32 planters, patios, or adjacent to windows where steam may cause fogging. Vent The vent termination shall be located at least 4′ horizontally Maintain 12″...
  • Page 32 Do not use field supplied couplings to extend the pipes. Concentric Termination Kit Airflow restriction will occur and the furnace pressure switch Table 5 NAHA001CV & NAHA002CV Venting may cause intermittent operation. Table for N9MPD & *9MPD Models Rain Cap to Vent Pipe Assembly 40,000, 50,000, 60,000, 75,000 &...
  • Page 33: Gas Supply And Piping

    Concentric Vent and Combustion- - Concentric Vent Sidewall Figure 36 Figure 35 Air Side Termination Attachment Roof Overhang Strap Combustion (Field Supplied) Vent 12″ min. 1″ max. Vent Combustion Flush to 1″ max. Combustion Vent 45° Elbow (Field Supplied) 25--22--02 Note: Securing strap must be field installed to prevent movement of termination kit in side wall.
  • Page 34 WARNING Use two pipe wrenches when making connections to prevent gas valve from turning. Install a manual shut--off valve external to furnace casing FIRE OR EXPLOSION HAZARD. and tighten all joints securely. Failure to follow this warning could result in If local codes allow the use of flexible gas appliance personal injury, death and/or property damage.
  • Page 35 Additional Propane Connection Requirements Alternate BTUH Input Ratings (USA Only) The input rating of these furnaces can be changed from the Have a licensed Propane gas dealer make all connections standard input rating to the alternate input rating shown in Table 8, at storage tank and check all connections from tank to by changing the main burner orifices.
  • Page 36 NATURAL GAS MANIFOLD PRESSURE (in wc) Table 11 FOR THE 40k, 60k & 80k BTUH MODEL AND ALTERNATE INPUT MODELS 20,000 BTU per burner MEAN ELEVATION FEET ABOVE SEA LEVEL HEATING 0 to 2001 to 3001 to 4001 to 5001 to 6001 to 7001 to VALUE...
  • Page 37: Electrical Wiring

    Changing Orifices for High Altitude Final Gas Piping Check WARNING WARNING FIRE OR EXPLOSION HAZARD. ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD. Failure to follow this warning could result in Failure to follow this warning could result in personal injury, death, and/or property damage. personal injury, death and/or property damage.
  • Page 38: Furnace Control

    Junction Box (J- Box) Relocation Furnace Control The furnace control is preset at the factory with a fixed blower ON The J--Box is installed on left side of casing. An alternate J--Box delay of 30 seconds in the heating mode. The blower OFF timing is location on right side can be used.
  • Page 39 8. Ductwork and Filter WARNING Side Return Air Cutout Figure 42 CARBON MONOXIDE POISONING HAZARD. A = 14 ″ Height of Cutout for 16″ x 25″ Filter Failure to follow this warning could result in B = 22 ″ Width of Cutout for 16″ x 25″ Filter personal injury or death.
  • Page 40 Figure 46 Standoff Filter Rack Side Mounted Filter Rack Figure 43 Using Optional Standoff Filter Rack 25--20--90 Filter Installation using Optional Filter Rack 25--21--45a When installing or removing a bottom mounted filter, slide the two CAUTION side filter clips to the back of the furnace BEFORE installing or removing.
  • Page 41 Subbase for Combustible Floor downflow furnace is set on a combustible floor, even when the furnace is installed on a coil box. NOTE: The three(3) screws in the top panel of the furnace next to Cut the opening in the floor according to Table 13. The hole the duct flange MUST be removed to provide serviceability of the in the floor must be cut to the dimensions listed in Table 13 primary heat exchangers in the downflow installation...
  • Page 42: Checks And Adjustments

    This subbase for combustible floors has been designed so that the Figure 49 Setting the Subbase height of the subbase raises the downflow coil off the floor to allow easy installation of the condensate drain. See Figure 50. Furnace/Coil Box Figure 50 Condensate Line Raised by Base Installation of...
  • Page 43: Main Burner Flame Check

    Turn OFF gas supply to all appliances and start furnace. To check temperature rise,use the following procedure: Use jumper wire on R to W for Heat. Place thermometers in supply and return air registers as Time how many seconds it takes the smallest dial on the gas close to furnace as possible, avoiding direct radiant heat meter to make one complete revolution.
  • Page 44: Furnace Maintenance

    If the same speed must be used for both heating and circulating blower compartment for operation of the continuous fan cooling, remove the undesired motor speed lead from the option. This connection is intended for the low speed motor tap, “Heat”...
  • Page 45 11. Sequence of Operation & Diagnostics The following is the normal operating sequence. Cooling (Y) Request: 24VAC signals applied to Y & G terminals of FCB (furnace control board) • Cool motor speed is energized after 5 second Cool Fan On Delay time. Y &...
  • Page 46 Heating Request with Gas Shut Off: 24 VAC signal applied to W terminal of FCB. The FCB will attempt 4 cycles for ignition then go to soft lockout for 3 hours then try for ignition again as long as the heat call remains. Power reset will clear lockout.
  • Page 47 Four Position Furnace Models Single Pipe Dual Certified N9MP1040B08C2 N9MPD040F08A2 N9MP1050B12C2 N9MPD050F12A2 N9MP1060B12C2 N9MPD060F12A2 N9MP1075B12C2 N9MPD075F12A2 N9MP1080F16C2 N9MPD080J16A2 N9MP1100F14C2 N9MPD100J14A2 N9MP1100J20C2 N9MPD100J20A2 N9MP1125J20C2 N9MPD125L20A2 Two Pipe Dual Certified N9MP2050B12C2 *9MPD050F12C2 N9MP2075B12C2 *9MPD075F12C2 N9MP2080F16C2 *9MPD080J16C2 N9MP2100F14C2 *9MPD100J14C2 N9MP2100J20C2 *9MPD100J20C2 N9MP2125J20C2 *9MPD125L20C2 * Denotes Brand International Comfort Products, LLC Lewisburg, TN 37091 U.S.A.
  • Page 48 Model Specifications Manufacturers Number (Mfr No - -See Rating Plate) ALL Models Specifications (N9MP1) N9MP1040B08C N9MP1050B12C N9MP1060B12C N9MP1075B12C General Gas Type Nat./Propane Nat./Propane Nat./Propane Nat./Propane Input (Btuh) 40,000 50,000 60,000 75,000 Output (Btuh) 36,000 45,500 54,000 68,000 Transformer Size (VA) T’stat Heat Anticipator...
  • Page 49 Model Specifications Manufacturers Number (Mfr No - -See Rating Plate) ALL Models Specifications (N9MP1) N9MP1080F16C N9MP1100F14C N9MP1100J20C N9MP1125J20C General Gas Type Nat./Propane Nat./Propane Nat./Propane Nat./Propane Input (Btuh) 80,000 100,000 100,000 125,000 Output (Btuh) 72,000 91,000 96,500 113,750 Transformer Size (VA) T’stat Heat Anticipator...
  • Page 50 Manufacturers Number (Mfr No - -See Rating Plate) ALL Models Specifications (N9MP2) N9MP2050B12C N9MP2075B12C N9MP2080F16C N9MP2100F14C N9MP2100J20C N9MP2125J20C General Gas Type Nat./Propane Nat./Propane Nat./Propane Nat./Propane Nat./Propane Nat./Propane Input (Btuh) 50,000 75,000 80,000 100,000 100,000 125,000 Output (Btuh) 45,500 68,000 72,000 91,000 96,500 113,750...
  • Page 51 Manufacturers Number (Mfr No - -See Rating Plate) ALL Models Specifications (N9MPD) N9MPD040F12A N9MPD050F12A N9MPD060F12A N9MPD075F12A General Gas Type Nat./Propane Nat./Propane Nat./Propane Nat./Propane Input (Btuh) 50,000 75,000 40,000 60,000 Output (Btuh) 46,000 69,000 37,000 55,000 Transformer Size (VA) T’stat Heat Anticipator Temp.
  • Page 52 Manufacturers Number (Mfr No - -See Rating Plate) ALL Models Specifications (N9MPD) N9MPD080J16A N9MPD100J14A N9MPD100J20A N9MPD125L20A General Gas Type Nat./Propane Nat./Propane Nat./Propane Nat./Propane Input (Btuh) 80,000 100,000 100,000 125,000 Output (Btuh) 73,600 92,000 92,000 115,000 Transformer Size (VA) T’stat Heat Anticipator Temp.
  • Page 53 Manufacturers Number (Mfr No - -See Rating Plate) ALL Models Specifications (*9MPD) *9MPD050F12C *9MPD075F12C *9MPD080J16C *9MPD100J14C *9MPD100J20C *9MPD125L20C General Gas Type Nat./Propane Nat./Propane Nat./Propane Nat./Propane Nat./Propane Nat./Propane Input (Btuh) 50,000 75,000 80,000 100,000 100,000 125,000 Output (Btuh) 46,000 69,000 73,600 92,000 92,000 115,000...
  • Page 54 CIRCULATION AIR BLOWER DATA (CFM#) N9MP1040B08 (1)(5) N9MPD040F08 (1)(5) Speed Speed Med L Med H Med L Med H ------ 1009 ------ 1079 ------ ------ 1032 ------ ------ ------ ------ ------ ------ ------ ------ ------ ------ ------ ------ ------ ------ ------ ------ ------...
  • Page 55 N9MP1075B12, N9MP2075B12 (1)(5) N9MPD075F12, *9MPD075F12 (1)(5) * Denotes Brand Speed Speed Med L Med H Med L Med H 1163 1368 1163 1368 1120 1319 1120 1319 1076 1263 1076 1263 1031 1202 1031 1202 1148 1148 1077 1077 ------ ------ ------ ------...
  • Page 56 N9MPD125L20, *9MPD125L20 (2)(5) * Denotes Brand N9MP1125J20, N9MP2125J20 (2)(4)(5) Speed Speed Med L Med H Med L Med H 1720 1910 2127 2315 1720 1910 2127 2315 1686 1881 2087 2268 1686 1881 2087 2268 1644 1833 2024 2201 1644 1833 2024 2201...
  • Page 57 Wiring Diagram (Single Stage, PSC Blower Motor) 440 01 1024 01 Specifications are subject to change without notice...
  • Page 58 N9MP1, N9MP2, N9MPD or *9MPD 440 01 1024 01 Specifications are subject to change without notice...
  • Page 59 Replacement Parts - N9MP1 & N9MP2 Models -- N9MP1040B08C2, N9MP1050B12C2, N9MP1060B12C2, N9MP1075B12C2, N9MP1080F16C2, N9MP1100F14C2, N9MP1100J20C2 & N9MP1125J20C2 -- N9MP2050B12C2, N9MP2075B12C2, N9MP2080F16C2, N9MP2100F14C2, N9MP2100J20C2 & N9MP2125J20C2 (Natural Gas) Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
  • Page 60 Replacement Parts - N9MP1 & N9MP2 Models -- N9MP1040B08C2, N9MP1050B12C2, N9MP1060B12C2, N9MP1075B12C2, N9MP1080F16C2, N9MP1100F14C2, N9MP1100J20C2 & N9MP1125J20C2 -- N9MP2050B12C2, N9MP2075B12C2, N9MP2080F16C2, N9MP2100F14C2, N9MP2100J20C2 & N9MP2125J20C2 (Natural Gas) Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
  • Page 61 Replacement Parts - N9MP1 & N9MP2 Models -- N9MP1040B08C2, N9MP1050B12C2, N9MP1060B12C2, N9MP1075B12C2, N9MP1080F16C2, N9MP1100F14C2, N9MP1100J20C2 & N9MP1125J20C2 -- N9MP2050B12C2, N9MP2075B12C2, N9MP2080F16C2, N9MP2100F14C2, N9MP2100J20C2 & N9MP2125J20C2 (Natural Gas) Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
  • Page 62 Replacement Parts - N9MP1 & N9MP2 Models -- N9MP1040B08C2, N9MP1050B12C2, N9MP1060B12C2, N9MP1075B12C2, N9MP1080F16C2, N9MP1100F14C2, N9MP1100J20C2 & N9MP1125J20C2 -- N9MP2050B12C2, N9MP2075B12C2, N9MP2080F16C2, N9MP2100F14C2, N9MP2100J20C2 & N9MP2125J20C2 (Natural Gas) Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
  • Page 63 Replacement Parts - N9MPD Models -- N9MPD040F08A2, N9MPD050F12A2, N9MPD060F12A2, N9MPD075F12A2, N9MPD080J16A2, N9MPD100J14A2, N9MPD100J20A2 & N9MPD125L20A2 (Natural Gas) Replacement part supplied will be current active part. For parts not listed, consult place of purchase. Description Part N9MPD Functional Number 040F08A 050F12A 060F12A 075F12A 080J16A...
  • Page 64 Replacement Parts - N9MPD Models -- N9MPD040812A2, N9MPD050F12A2, N9MPD060F12A2, N9MPD075F12A2, N9MPD080J16A2, N9MPD100J14A2, N9MPD100J20A2 & N9MPD125L20A2 (Natural Gas) Replacement part supplied will be current active part. For parts not listed, consult place of purchase. N9MPD Description Part Non- Functional Number 040F08A 050F12A 060F12A 075F12A...
  • Page 65 Replacement Parts - N9MPD Models -- N9MPD040F08A2, N9MPD050F12A2, N9MPD060F12A2, N9MPD075F12A2, N9MPD080J16A2, N9MPD100J14A2, N9MPD100J20A2 & N9MPD125L20A2 (Natural Gas) Replacement part supplied will be current active part. For parts not listed, consult place of purchase. N9MPD Description Part Non- Functional Number 040F08A 050F12A 060F12A 075F12A...
  • Page 66 Replacement Parts - N9MPD Models -- N9MPD040F08A2, N9MPD050F12A2, N9MPD060F12A2, N9MPD075F12A2, N9MPD080J16A2, N9MPD100J14A2, N9MPD100J20A2 & N9MPD125L20A2 (Natural Gas) Replacement part supplied will be current active part. For parts not listed, consult place of purchase. N9MPD Description Part Non- Functional Number 040F08A 050F12A 060F12A 075F12A...
  • Page 67 Replacement Parts - *9MPD Models -- *9MPD050F12C2, *9MPD075F12C2, *9MPD080J16C2, *9MPD100J14C2, *9MPD100J20C2 & *9MPD125L20C2 (Natural Gas) *Denotes Brand Replacement part supplied will be current active part. For parts not listed, consult place of purchase. Description Part *9MPD Functional Number 050F12C 075F12C 080J16C 100J14C 100J20C...
  • Page 68 Door, Blower (Tempstar only) 1173015 (Tempstar only) 1173016 (Tempstar only) 1173082 (Comfortmaker/Keeprite only) 1173009 (Comfortmaker/Keeprite only) 1173010 (Comfortmaker/Keeprite only) 1173072 (Heil/Arcoaire only) 1173012 (Heil/Arcoaire only) 1173013 (Heil/Arcoaire only) 1173075 Bracket, Door Filler 1172232 1172233 1172234 Door, Front (Tstar only) 1013154...
  • Page 69 Replacement Parts - *9MPD Models -- *9MPD050F12C2, *9MPD075F12C2, *9MPD080J16C2, *9MPD100J14C2, *9MPD100J20C2 & *9MPD125L20C2 (Natural Gas) *Denotes Brand Replacement part supplied will be current active part. For parts not listed, consult place of purchase. *9MPD Description Part Non- Functional Number 050F12C 075F12C 080J16C 100J14C...
  • Page 70 Replacement Parts - *9MPD Models -- *9MPD050F12C2, *9MPD075F12C2, *9MPD080J16C2, *9MPD100J14C2, *9MPD100J20C2 & *9MPD125L20C2 (Natural Gas) *Denotes Brand Replacement part supplied will be current active part. For parts not listed, consult place of purchase. *9MPD Description Part Non- Functional Number 050F12C 075F12C 080J16C 100J14C...

This manual is also suitable for:

N9mpdN9mp2T9mpdH9mpdC9mpd

Table of Contents