ABB REM610 Product Manual page 18

Relion 610 series motor protection
Hide thumbs Also See for REM610:
Table of Contents

Advertisement

Motor Protection
REM610
Product version: C
Table 16. Electromagnetic compatibility tests, continued
Description
REM610CxxHxxx
• Common mode
• Differential mode
REM610CxxLxxx and
REM610CxxxxMx
• Common mode
• Differential mode
Voltage dips and short
interruptions
Electromagnetic emission
tests
• Conducted, RF-emission
(Mains terminal)
• Radiated RF-emission
CE compliance
Table 17. Insulation tests
Description
Dielectric tests
• Test voltage
Impulse voltage test
• Test voltage
Insulation resistance
measurements
• Isolation resistance
18
Type test value
Class A
300 V rms
150 V rms
Class B
300 V rms
100 V rms
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Type test value
2 kV, 50 Hz, 1 min
5 kV, unipolar impulses,
waveform 1.2/50 μs, source
energy 0.5 J
>100 MΏ, 500 V DC
1MRS756304 C
Issued: 30.10.2009
Reference
IEC 61000-4-11
EN 55011
EN 55011, class A, IEC
60255-25
EN 55011, class A, IEC
60255-25
Complies with the EMC
directive 2009/108/EC and
LV directive 2006/95/IEC
Reference
IEC 60255-5
IEC 60255-5
IEC 60255-5
ABB

Advertisement

Table of Contents
loading

Table of Contents