Technical Data - ABB REM610 Product Manual

Relion 610 series motor protection
Hide thumbs Also See for REM610:
Table of Contents

Advertisement

ABB
Motor Protection
REM610
Product version: C

12. Technical data

Table 3. Dimensions
Description
Width
Height
Depth
Weight
Table 4. Power supply
Description
Type
U
rated
aux
U
variation (temporary)
aux
Burden of auxiliary voltage
supply under quiescent (P
operating condition
Ripple in the DC auxiliary
voltage
Interruption time in the
auxiliary DC voltage without
resetting the IED
Time to trip from switching
on the auxiliary voltage
Internal over temperature
limit
Fuse type
1) Time to trip of stages I>>
Value
frame
case
frame
case
case
IED
spare unit
Value
REM610CxxHxxx
U
= 100/110/120/220/240 V
r
AC
U
= 110/125/220/250 V DC
r
85...110% of U
r
80...120% of U
r
<9 W/13 W
)/
q
Max. 12% of the DC value (at frequency ogf 100 Hz)
<50 ms at U
rated
aux
<350 ms
1)
+100 ºC
T2A/250 V
177 mm
164 mm
177 mm (4U)
160 mm
149.3 mm
3.5 kg
1.8 kg
REM610xxLxxx
U
= 24/48/60 V DC
r
(AC)
80...120% of U
(DC)
1MRS756304 C
Issued: 30.10.2009
(DC)
r
11

Advertisement

Table of Contents
loading

Table of Contents