Parameters/address space
4.3 Declaration of parameters
Smoothing
The individual measured values are smoothed using filtering. The smoothing can be set in 4
levels.
Smoothing time = number of module cycles (k) x cycle time of the module.
The following figure shows after how many module cycles the smoothed analog value is
almost 100%, depending on the set smoothing. Is valid for each signal change at the analog
input.
Figure 4-1
Hardware interrupt 1 or 2
Enable a hardware interrupt at violation of high limit 1 or 2 or low limit 1 or 2.
Low limit 1 or 2
Specifies the low limit threshold that triggers hardware interrupt 1 or 2.
High limit 1 or 2
Specifies the high limit threshold that triggers hardware interrupt 1 or 2.
30
None (k = 1)
Weak (k = 4)
Medium (k = 16)
Strong (k = 32)
Smoothing with AI 8xU/I HF