Siemens Simatic S7-1500 / ET 200MP Manual page 28

Analog input module ai 8xu/i hf
Table of Contents

Advertisement

Parameters/address space
4.2 Parameters
Parameters
Hardware interrupt
Hardware interrupt high
limit 1
Hardware interrupt low
limit 1
Hardware interrupt high
limit 2
Hardware interrupt low
limit 2
If you enable diagnostics for multiple channels, you will receive an alarm surge on failure of the supply voltage because
1)
each enabled channel will detect this fault.
You can prevent this message burst by assigning the diagnostics function to one channel only.
When "Wire break" diagnostics is disabled, the current limit of 1.185 mA applies to the value status. For measured
2)
values below 1.185 mA, the value status is always: 0 = fault.
You can set the effective range of the diagnostics for each channel in the user program with data records 0 to 7.
3)
You can set the current limit for wire break diagnostics, the "Hardware interrupt" parameter, the "Measuring range ad-
4)
justment high and low limit" and the hardware interrupt limits in the user program with data records 0 to 7.
28
Range of values
Default set-
ting
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
Configuration
Scope with configuration software, e.g.,
in RUN
Integrated in the
hardware cata-
log STEP 7
(TIA Portal) as
of V13 or GSD
file PROFINET
IO
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Analog Input Module AI 8xU/I HF (6ES7531-7NF00-0AB0)
Manual, 09/2016, A5E36649087-AB
STEP 7 (TIA Portal)
GSD file
PROFIBUS DP
---
4)
---
4)
---
4)
---
4)