Siemens 6SE2101–1AA01 Operating Manual page 24

6se21 series simovert p
Table of Contents

Advertisement

Available languages

Available languages

Parameter
Description
Number
Analogue Inputs
P04
(continued)
0–10 V input (X11.7)
0–20 mA input (X11.9)
4–20 mA input (X11.9)
P05
RUN/STOP mode
(see section 5.1.1 for
detailed explanation)
P06
Voltage to frequency curve
selection
VOLTAGE
100
VOLTAGE
100
VOLTAGE
100
Display
Setting
(Factory
Setting)
50
400
FREQUENCY
60
400
FREQUENCY
400
87
FREQUENCY
5/7
Notes
007
0 V = minimum frequency P07.
10 V = maximum frequency P08.
008
0 mA = minimum frequency P07.
20 mA = maximum frequency P08.
009
4 mA = minimum frequency P07.
20 mA = maximum frequency P08.
(000)
Note: Additional fixed frequencies are
programmable using parameter P24, which
overrides this operating mode.
000
Ramp–down; edge–triggered; trip inactive.
001
Ramp–down; level–triggered; trip inactive.
002
Free run; edge–triggered; trip inactive.
003
Free run; level–triggered; trip inactive.
004
Ramp–down; edge–triggered; trip active.
005
Free run; edge–triggered; trip active.
006
Ramp–down; level–triggered; trip active.
007
Free run; level–triggered; trip active.
008
Ramp–down; push–button control.
009
Free run; push–button control.
(000)
000
Linear 0–50 Hz
100% 50–400 Hz
001
Linear 0–60 Hz
100% 60–400 Hz
002
Linear 0–87 Hz
100% 87–400 Hz
English