Parameter
Description
Number
P27
Third Fixed Frequency
P28
Fourth Fixed Frequency
P29
Skip Frequency
P30
Tachometer Mode
P31∗
Tachometer Scale Factor
P32∗
Feedback Compensation:
Proportional Term (%)
P33∗
Feedback Compensation:
Integral Term (%)
P34∗
Feedback Compensation:
Differential Term (%)
P35∗
Tachometer Slip Limit (Hz)
P36∗
Tachometer Sample Rate
5/12
Display
Setting
Notes
(Factory
Setting)
00.0 –
Fixed frequency.
400
(00.0)
00.0 –
Fixed frequency.
400
(00.0)
00.0 –
This parameter allows a skip frequency to be
400
selected. Operation of the inverter will be inhibited
over the range (skip frequency – 2 Hz) to (skip
frequency + 2 Hz). If a frequency in this range is
selected, the lower or higher frequency will be
selected and displayed. Note that during ramping
the frequency output will ramp continuously and
not 'step' through the skip range.
(00.0)
This parameter enables the tachometer input
and selects the tachometer calculation rate. See
section 6 for further details of tachometer
applications.
000
Tachometer input disabled.
001
Normal feedback.
002
Feedback control suspended during ramping.
003
As 001, except output disabled when frequency
falls to P07 (minimum frequency).
004
As 002, except output disabled when frequency
falls to P07 (minimum frequency).
(000)
00.1 –
Frequency at 50 V tacho input.
999
See section 6 for further details.
(50.0)
000 –
See section 6 for further details.
999
(050)
000 –
See section 6 for further details.
250
(000)
000 –
See section 6 for further details.
250
(000)
00.0 –
See section 6 for further details.
20.0
(05.0)
001 –
n x 30 ms
200
See section 6 for further details.
(001)
English