Connector
J10/J11
(7)
J10 for
Access
Point A
J10/J11
J11 for
(8)
Access
Point B
J11 (9)
J8/J7 (1)
J8/J7 (2)
J8 for
Access
Point A
J8/J7 (3) D1/CLK
J7 for
Access
Point B
J8/J7 (4) DATA
J8/J7 (5) GND
ACCESS CONTROL PANEL CONNECTIONS
PIM400-TD2
signal
Request to Exit input
REQ TO EXIT
Request to Exit
common contact
(GND)
+5V
5 VDC
Normally Open
strike relay contact
STRIKE
INPUT
Common strike relay
contact
Clock or Data 1
output
Data or Data 0 input
Signal ground
ACP signal
PIM400-TD2 output indicating
when the access point interior
door handle is making a request
to exit.
Connect to the ACP request to
exit input.
Connect only if the access point
needs to have request to exit
function.
The request to exit signal polarity
can be configured using the
SUS. This setting is shared with
the request to enter signal.
Output is pulled-up to 5 VDC and
can sink 50mA.
RESERVED
5 VDC power supply pin for the
RLBD, dry contact relay board.
Strike input monitors the access
panel strike relay.
Connect the STRIKE signal to
the normally open terminal of the
strike relay.
Connect the GROUND signal
to the common terminal of the
strike relay.
Connect only if the access point
needs to be unlocked (door) or
raised (gate).
PIM400-TD2 outputs used to
present card data to the ACP.
For an access point with a
magnetic reader, will present
clock and data signals to the ACP.
For an access point with a
Wiegand or proximity reader, will
present data1 and data0 signals
to the ACP.
If initial hookup fails to operate,
switch wires at these terminals.
Output is pulled-up to 3.6 VDC
and can sink 50mA.
Common signal ground for
the EXIT REQ, DOOR STAT,
TROUBLE, DATA/D0 and CLK/
D1 signals.
Description/Explanation
11 • Schlage • PIM400-TD2 user guide