16.2. Sensible Capacity Chart
16.2.1.
CS-YW9GKE
230V
Indoor wet
bulb temp.
TC
17.0°C
2.48
19.0°C
19.5°C
2.72
22.0°C
2.97
16.2.2.
CS-YW12GKE
230V
Indoor wet
bulb temp.
TC
17.0°C
3.08
19.0°C
19.5°C
3.38
22.0°C
3.68
TC
-
Total Cooling Capacity (kW)
SHC
-
Sensible Heat Capacity (kW)
IP
-
Input Power (kW)
30
SHC
IP
TC
SHC
1.88
0.82
2.32
2.50
1.97
0.84
2.55
2.04
0.85
2.77
30
SHC
IP
TC
SHC
2.33
1.04
2.87
3.10
2.44
1.05
3.16
2.53
1.07
3.44
Outdoor Temp. (°C)
35
IP
TC
SHC
1.80
0.88
2.16
1.73
0.90
1.89
0.90
2.37
1.82
1.96
0.91
2.58
1.89
Outdoor Temp. (°C)
35
IP
TC
SHC
2.24
1.11
2.67
2.15
1.13
2.34
1.13
2.94
2.26
2.43
1.15
3.20
2.35
47
40
46
IP
TC
SHC
0.94
1.96
1.65
0.96
2.15
1.73
0.98
2.35
1.81
40
46
IP
TC
SHC
1.19
2.43
2.04
1.21
2.67
2.15
1.24
2.91
2.24
Indoor 27°C/19°C
Outdoor 35°C/24°C
IP
1.02
1.04
1.06
IP
1.28
1.31
1.33