1.5 SPECIFICATIONS

The UPS name plate displays the rated kVA as well as nominal voltages and currents. The
name plate is located on the inside of the UPS front door.

TABLE 1.3 Power Specifications

Rated output
Power
3 phase / 3 wire
100kVA / 80kW
150kVA / 120kW
225kVA / 180kW
300kVA / 270kW
375kVA / 338kW
500kVA / 450kW
750kVA / 675kW

TABLE 1.4 UPS Module Information

UPS
Cable
Width
[kVA]
Entry
[in / mm]
100
BOTTOM
43.3 / 1100
150
BOTTOM
47.2 / 1200
225
BOTTOM
55.1 / 1400
300
TOP
76.8 / 1950
375
TOP
76.8 / 1950
500
TOP
114.2 / 2900
750
TOP
129.9 / 3300
MITSUBISHI ELECTRIC 9800A SERIES UPS
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Input voltage
Bypass input voltage
3 phase / 4 wire
480V
480V or 600V
480V
480V or 600V
480V
480V or 600V
480V
480V or 600V
480V
480V or 600V
480V
480V or 600V
480V
480V or 600V
Depth
[in / mm]
29.8 / 758
29.8 / 758
29.8 / 758
37.7 / 958
37.7 / 958
37.7 / 958
49.5 / 1258
Page Number:
Output voltage
3 phase / 3 or 4 wire
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
Height
Weight
[in / mm]
[lb./ kg]
79.7 / 2025
2061 / 935
79.7 / 2025
2579 / 1170
79.7 / 2025
3263 / 1480
79.7 / 2025
4564 / 2070
79.7 / 2025
4916 / 2230
79.7 / 2025
6923 / 3140
79.7 / 2025
9193 / 4170
1-15
Heating
[kBTH / h]
19
28
43
59
73
89
134