Figure 2.17 Remote "Start" Contact Connections - Mitsubishi Electric 9800A Owner Technical Manual

9800a series uninterruptible power supply system
Hide thumbs Also See for 9800A:
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC
OWNERS / TECHNICAL MANUAL
The UPS is equipped with a selectable output contact feature.
NOTE:
The above alarms are the default settings. Contact MITSUBISHI
ELECTRIC POWER PRODUCTS, INC for setup information
B) Input Contacts (for remote access of UPS)
External contacts are provided by the user of the UPS system. Terminal voltage at the
UPS is 24Vdc. Provide external dry contact accordingly.
Do not apply voltages to remote access input terminals.
CAUTION:
Damage to UPS may result
Refer to Figure 2.17 for a typical wiring configuration. Although this figure applies to
the remote start/stop terminals, the same wiring arrangement is used for emergency
stop; battery liquid low; and battery temperature high.

FIGURE 2.17 Remote "Start" Contact Connections

UPS Cabinet
Relay Coil current : 8.3mA
Details of input contacts for remote access : TN2
Terminals 1 to 2
Remote "Inverter Start" input terminal (IN1)
Used to start inverter from a remote location. UPS must be programmed for
remote operation. Refer to Operations Menu for procedure.
Terminals 3 to 4
Remote "Inverter Stop" input terminal (IN2)
Used to stop inverter from a remote location. UPS must be programmed for
remote operation. Refer to Operations Menu for procedure.
Terminals 5 to 6
"Battery Temp. High" contact input (IN3)
Input fed by a thermocouple that monitors battery temperature. The
converter float voltage level is reduced for battery over-temperature
conditions. External thermocouple is user supplied
MITSUBISHI ELECTRIC 9800A SERIES UPS
9800A SERIES UPS
.
Relay
Coil
24 VDC
Page Number:
2-11
External to UPS
Cabinet
Start
Common
ON
OFF
Use Momentary Switches Only
User supplied
.
Start
Switch
0.5S - 4S