Applications
Features
Additional features
Functions
6/81
Siemens
Building Technologies
2

Summary

2.1

Brief description

2-pipe fan coil units, 2-pipe with electric heater, 2-pipe with radiator/floor heating
4-pipe fan coil units, 4-pipe with electric heater
2-stage heating or cooling application
Compressors in dx-type equipment
Universal heating and/or cooling
2 multifunctional inputs and 1 digital input for keycard contact, external sensor, etc.
Operating modes: Comfort, Economy and Protection
Automatic or manual heating/cooling changeover
Adjustable commissioning and control parameters
Minimum and maximum setpoint limitation
Backlit LCD
Selection of fan stage in the dead zone via P15
RDG100/RDG100T..:
On/Off, PWM or 3-position control outputs (triacs)
Output for 3-speed or 1-speed fan
AC 230 V operating voltage
RDG110..:
On/Off control outputs (relay, SPDT)
Output for 3-speed or 1-speed fan
AC 230 V operating voltage (RDG110)
AC/DC 24 V operating voltage (RDG110U)
RDG160T..:
DC 0...10 V or On/Off control outputs for actuators
DC 0...10 V or relay outputs for fan (ECM or 1-/3- speed)
AC/DC 24 V operating voltage
RDG100T, RDG160T.., RDG100T/H:
Infrared remote control receiver
Auto Timer mode with 8 programmable timers
Auto timer can be disabled via P02
Auto timer can be disabled via DIP switches (RDG160T..)
Landscape design (only RDG100T/H)
Maintenance of room temperature via built-in temperature sensor or external room
temperature/return air temperature sensor
Automatic or manual changeover between heating and cooling mode
Selection of applications via DIP switches
Selection of operating mode via the operating mode button on the thermostat
1-speed, 3-speed or DC...10 V fan control (automatic or manual)
Display of current room temperature or setpoint in °C and/or °F
Minimum and maximum setpoint limitation
Button lock (automatic or manual)
1 digital input, freely selectable for:
– Operating mode switchover contact (keycard)
– Automatic heating/cooling changeover contact
– Electric heater enable
– Dewpoint sensor
RDG100.., RDG110.., RDG160T.. Basic Documentation
Summary
CE1P3181en