Electrical Connection - Daikin FDM75DXV1 Installation Manual

Air cooled, ducted split type air-conditioners (d & e series) r22 cooling only r407c cooling only r22 heatpump r407c heatpump
Table of Contents

Advertisement

IMPORTANT: * These values are for information only, they should be checked and selected to comply with the local and/or
national codes and regulations. They are also subjected to the type of installation and size of conductors.
** The appropriate voltage range should be checked with data label on the unit.
Cooling Unit
FDM(P) 75/100D
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
Model
Voltage range**
Power supply cable size* /mm²
A) Indoor
B) Outdoor
C) Total
Number of conductors
A) Indoor
B) Outdoor
Interconnection cable size* / mm²
Number of conductors
Recommended time delay fuse* /A
A) Indoor
B) Outdoor
C) Total
FD(P) 125/150D
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.

ELECTRICAL CONNECTION

R
S
Power Supply Cable
Indoor
Outdoor
Indoor
Outdoor
R
S
Power Supply Cable
Power Supply Cable
T
N
L
COMP
L
N
COMP
FDM(P) 75D
RC(P) 75D
220-240V/1PH/50Hz+ !
380-415V/3PH/50Hz+ !
1
2.5
2.5
-
5
1
4
10
25
32
T
N
L
COMP
R
S
T
L
COMP
1-14
N
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
FDM(P) 100D
RC(P) 100D
1
4
4
-
5
1
4
12
32
40
N
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
N