COM600 series, Version 4.1
SNMP OPC Server User's Manual
The new preconfigured objects appear in the object tree. If the configuration file is large,
the import may take time. To import a configuration file for a different device, right-
click the device, select SCL Import again and repeat the steps above.
For more information about the SCL Import function, see COM600 User's Manual.
Adding Logical Device objects
To add a Logical Device object:
1. Select an SNMP IEC object and right-click it.
2. Select New > New or New > Communication > SNMP LD.
Each SNMP IED must have at least one Logical Device object
as a child object.
Adding Logical Node objects
To add a Logical Node:
1. Select a Logical Device object and right-click it.
2. Add a Logical Node object.
3. Rename the new object. The names of the Logical Node objects have to be unique.
You should have only one Logical Node 0 (LLN0) as a child
object to a Logical Device object.
Adding data objects
To add a data object:
1. Select a Logical Node object and right-click it.
2. Add a data object.
3. Rename the new object. The names of the data objects have to be unique. However,
you can have a data object with same name under a different Logical Node.
Configuring objects
General about configuring objects
After the objects have been added, configure the object properties. Figure 3.4.1-1 shows
an example of how to use SAB600 to configure the object properties for SNMP OPC
Server.
1MRS757276