The new preconfigured objects appear in the object tree. If the configuration file is large,
the import may take time. To import a configuration file for a different device, right-
click the device, select SCL Import again and repeat the steps above.
For more information about the SCL Import function, see COM600 User's Manual.

Adding Logical Device objects

To add a Logical Device object:
1. Select an SNMP IEC object and right-click it.
2. Select New > New or New > Communication > SNMP LD.
Each SNMP IED must have at least one Logical Device object
as a child object.

Adding Logical Node objects

To add a Logical Node:
1. Select a Logical Device object and right-click it.
2. Add a Logical Node object.
3. Rename the new object. The names of the Logical Node objects have to be unique.
You should have only one Logical Node 0 (LLN0) as a child
object to a Logical Device object.

Adding data objects

To add a data object:
1. Select a Logical Node object and right-click it.
2. Add a data object.
3. Rename the new object. The names of the data objects have to be unique. However,
you can have a data object with same name under a different Logical Node.

Configuring objects

General about configuring objects

After the objects have been added, configure the object properties. Figure 3.4.1-1 shows
an example of how to use SAB600 to configure the object properties for SNMP OPC
Server.