Download Print this page

Installation Instructions; Connections And Terminal Assignment; Disconnection Characteristic (Typical) - Siemens 6EP1961-2BA00 Operating Instructions Manual

Sitop select diagnosis module
Hide thumbs Also See for 6EP1961-2BA00:

Advertisement

Available languages

Available languages

Saving the set time delay: On pressing the reset button (5) permanently for approx. 8 s in the programming mode after setting the time delay, all LEDs (3) are
red. If the reset button is released then, the diagnosis module stores the set time delay and switches on the outputs sequentially. Now the diagnosis module is
in its normal operating mode again. If the reset button is not pressed within 30 s in the programming mode, the diagnosis module automatically switches back
to the normal operation mode without storing a change of time delay. If the supply voltage fails during programming, there will also be no storage.
!
Note: The outputs of the diagnosis module are disconnected during the programming mode. After manual or automatic leaving of programming mode as
well as resumption of power supply after breakdown, the outputs will be switched on automatically!

Installation instructions

Installation on DIN rail (DIN EN 50022-35x7.5/15). The equipment must be installed vertically with the input terminals at the bottom and the output terminals at
the top, in order to ensure adequate heat dissipation. A clearance of at least 50 mm must be allowed above and below the device.
To snap the unit on to the DIN bar, hang it with its nose (A) into the bar (C)  a nd press until the spring (B)  s naps into place (see page 2). If difficulty is
experienced in snapping the unit on to the bar, loosen the spring (B)  slightly as described under "Removing the Power Supply Unit". To remove from the DIN
bar, use a screw driver to loosen the spring (B)  i n the direction of the arrow.
The 24 V DC supply voltage (8) must be connected in accordance with the national standards. It is only allowed to be connected to a power supply with "safe
electrical isolation" in accordance with EN 60950.
!
Note: The 0 V connection (7) of the device merely serves to supply the internal electronic circuits. The 0 V of the loads must be supplied directly to the
power supply by means of separate lines.
In Ex - applications must be guaranteed that installation is according to protection class IP 54.

Connections and terminal assignment

Terminals
Function
Input +24 V
+24 V input voltage connection (from "+"
output of the power supply)
Input 0 V
0 V connection for supplying the internal
electronic circuits (from "–" output of the
power supply)
Output
Outputs of the diagnosis module for
1, 2, 3, 4
connecting the load circuits
13, 14
Common signaling contact

Disconnection characteristic (typical):

100,0sec
10,0sec
1,0sec
0,1sec
0,0sec
0%
20%
40%
Supply voltage > 20 V and the following power requirement for the branch concerned:
▪ 0 % to 100 % of setting
▪ 101 % to 130 % of setting
▪ > 130 % of setting
Supply voltage dip < 20 V and the following power requirement for the branch concerned:
▪ > 100 % of setting
Herausgegeben von:
SIMEA
Bereich IA SC
Siemensstraße 92
1210 Wien
Österreich
Siemens AG Österreich
SITOP select / 08.2013
Clamping range
0.33 to 10 mm
0.22 to 4 mm
0.22 to 4 mm
0.22 to 4 mm
5,0sec
0,10sec
60%
80%
100% 120% 140% 160%
I / Irated
► No disconnection
► Disconnection after approx. 5 s
► Current limited to approx. 130 %, disconnection after typ. 50 to 100 ms
► Immediate disconnection
Published by:
SIMEA
IA SC Group
Siemensstraße 92
1210 Vienna
Austria
Seite 6 von 6
Remarks
2
Screw terminals; use a screwdriver with 5 mm blade width; recommended
tightening torque 1.2 Nm.
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 to 0.7 Nm.
Note: The 0 V of the loads must be supplied directly to the power supply by
means of separate lines !
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 to 0.7 Nm.
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 to 0.7 Nm.
Liefermöglichkeiten und technische Änderungen vorbehalten
Availability and technical specifications subject to change without prior notice
Bestellnummer / Order number C98130-A7524-A1-7-7419
© Siemens AG Österreich 08/2013. All rights reserved