3
Placing the outdoor units
3-1. Anchor bolts position
A
B
3-2. Removing fasteners of compressor's leg
(Only applied to RVXVHT125F)
(1) Open the bottom cabinet with screw driver.
The compressors are fastened with nuts in 4 places of only
following models.
RVXVHT125F
(2) Detach nut washer, washer and stopper nut from
compressors with a tool.
Nut washer
Washer Stopper nut
(3) Refasten the nut washer only.
CAUTION
Pay your attention not to touch the copper pipes as detaching the fasteners.
The stopper nut and washer should be removed.
If this work is not conducted correctly, it can cause outdoor unit to vibrate and make much noise.
44
Model
A
B
Anchor bolt
Unit : mm(inch)
RVXVHT075/100
RVXVHT125
880(34-5/8)
1200(47-1/4)
738(29)
1058(41-5/8)
Remove