Space Requirements - Samsung DVM PLUS III Technical Data Book

Hide thumbs Also See for DVM PLUS III:
Table of Contents

Advertisement

2

Space requirements

2-1. Single installation
10(3/8) or more
2-2. Group installation
10(3/8)
or more
20(3/4) or more
600(24) or more
10(3/8)
or more
Note
 The installation space mentioned above is minimum suggested clearance.
 To secure enough service space and performance of system, take account of more sufficient space.
 The required minimum space between outdoor units for service and performance of system is at least
100mm(4in).
300(12) or more[S2]
10(3/8)
Front
or more
500(20) or more[S1]
Front
10(3/8)
or more
20(3/4) or more 20(3/4) or more
300(12)
or more
Front
Front
10(3/8)
or more
10(3/8)
500(20)
or more
20(3/4)
or more
or more
Front wall height
Rear wall height
Side wall height
If the height of the wall exceeds the above value,
more space should be added to the front and
rear space individually.
Wall height unrestricted
200(8) or more
Wall height unrestricted
300(12) or
more[S2]
300(12) or more
500(20) or
Front
more[S1]
200(8) or
more
20(3/4) or more
300(12)
or more
Front
500(20) or more
10(3/8) or
Front
more
300(12) or
more
20(3/4) or more
Unit : mm (inch)
300(12) or more
Unit : mm (inch)
Front
400(16)
or more
1500mm(60in) and less
500mm(20in) and less
Height unrestricted
Front : S1 + h1/2,
Rear : S2 + h2/2
41