1 Introduction
This document describes how to connect the IEC870-5-103 compliant communications interface to a control system or
interrogating computer.
To access the interface the user will need appropriate software within the control system or on the interrogating
computer (e.g. Reydisp Evolution).
2 Connection Specification and Relay Settings
This section defines the connection medium as defined by IEC 870-5-103. Appendix A shows some typical
communication connections.
2.1. Connection Method
Argus relays can be connected in either a Star or Ring fibre-optic communications network. If star
connected then a passive fibre optic hub must be used. A lower cost option is the ring configuration
where the Argus relays are 'daisy chained.' That is, the transmit output of the first relay is connected to
the receive input of the second relay, and so on until the ring is complete.
Communication to the ring may be achieved either locally in the substation or remotely via the Public
Switched Telephone Network (PSTN). If remote communication is desired, then additional modem
equipment must be installed.
Reydisp Evolution is a PC based software package providing capability for both local and remote
communication. It provides features such as download of disturbance and event records, upload of
relay settings, real-time monitoring of measurands and remote control of plant.
2.2. Transmission Method
The transmission method is Half Duplex serial asynchronous transmission. In IEC 870-5-103 the line
idle state is defined as Light ON. This can alternatively be selected as Light OFF in the
Communications Interface menu of the relay if required for use with alternate hardware (See Section
2.5).
2.3. Transmission Rate
Rates of 19200, 9600, 4800, 2400, 1200, 600, 300, 150, 110 and 75 bits per second (BPS) are
provided. Only 19200 and 9600 BPS are standard in IEC 870-5-103, the additional rates are provided
for local or modem communications.
2.4. Line Idle Setting
The line idle setting can be set to be either ON or OFF and the setting must be compatible with the
device connected to the relay. The IEC 870-5-103 standard defines a line idle state of Light On. If the
device the relay is connected to does not have a compatible fibre-optic port then a suitable electrical to
optical converter is required to connect it to a standard RS232C electrical interface. A suitable
converter is the Sigma 4 type, which is available from Reyrolle Protection.
Alternative converters are the Reyrolle Dual RS232 Port (Sigma 3) or Reyrolle Passive Fibre-Optic Hub
(Sigma 1).
1.
The Sigma 3 Dual RS232 port provides a fibre-optic interface to a relay and two RS232 ports.
The RS232 system port is typically connected to a control system while the second port is a local
port. When the local port is in use the system port is automatically disabled. The Sigma 3 has an
internal link to switch between line idle Light ON or Light OFF. The default configuration is Light
OFF.
2.
The Sigma 1 Passive Fibre-Optic Hub provides fibre-optic interfaces for up to 29 relays. It has a
fibre-optic port to the control system and multiple relay connections. Each of the 30 fibre-optic
ports can be configured for either Light ON or Light OFF operation. Default for all is OFF.