When installing a cassette type indoor unit on the ceiling and its installation condition is temperature over 27°C and
humidity over 80%, install a 10mm thickness of polyethylene insulation or similar type of insulation on the indoor unit
body.
Insulation installation guide
Cut the part where pipes are pulled out or some curved part for insulating work.
When insulating a connecting duct, the outlet and inlet part (front, back) should be
insulated together.
Thickness: more than 10mm
Indoor unit
4way Cassette <L>
(840x288x840)
Cassette type
4way Cassette <M>
(840x246x840)
4way Cassette <S>
(840x204x840)
Insulate the end of the pipe and some curved area by using separate insulator.
• The units must be installed according to distances declared, in
order to permit accessibility from each side,
either to guarantee correct operation of maintenance or
repairing products.
The unit's parts must be reachable and removable completely
under safety condition (for people or things).
• Do not hold the discharge while carrying the indoor unit to avoid the possibility of breakage. You must hold the
hanger plate on the corner and carry the indoor unit.
A
090FB4P
100FB4P
100FB4F
910X235
0904PX
1254X
1004PX
1004ZX
071FB4P
090FB4D
100FB4D
910X193
0714PX
0904DX
1004DX
052FB4D
910X151
071FB4D
0714DX
A
B
C
940X235
610X235
650X235
940X193
610X193
650X193
940X151
610X151
650X151
D
E
B
C
D
E
870X870
870X870
870X870
5