Airflow Adjustment; Electric Heat Airflow; Cooling Mode Dehumidification - Rheem RH1V2417STANJA Installation Instructions Manual

Featuring industry standard r-410a refrigerant
Hide thumbs Also See for RH1V2417STANJA:
Table of Contents

Advertisement

6.13 AIRFLOW ADJUSTMENT (-)H2V (TRIM)
FIGURE 33
DIP SWITCH SETTING FOR AIRFLOW ADJUSTMENTS
When not using the Comfort Control
can be tweaked +/-10% to suit the installation. To adjust the airflow, adjust DIP switches
5 and 6 per this table:
IMPORTANT: The DIP switches are active only when using conventional a 24VAC ther-
mostat. If using the Comfort Control
flows.
NOTE: Airflow adjustment is active for cooling operation only. Cooling airflow adjust-
ments are ignored when electric heat is activated.

6.14 ELECTRIC HEAT AIRFLOW

The RHPN-series air handlers are shipped with the "Low KW airflow" feature turned OFF.
Activate lower airflow feature for lower KW electric heat applications by turning DIP switch
8 ON.
IMPORTANT: The DIP switches are active only when using a conventional 24VAC ther-
mostat. If using the Comfort Control
flow adjustment.
ELECTRIC HEAT AIRFLOW FOR THE RHPN AIR HANDLERS (-)H2V
Air Handler
RH2V2421HTACJA00
RH2V3624HTACJA00
RH2V4824HTACJA00
RH2V6024HTACJA00

6.15 COOLING MODE DEHUMIDIFICATION

FIGURE 34
ON DEMAND DEHUMIDIFICATION DIP SWITCH (-)H2V
2
System™, the (-)H2V air handler cooling airflow
2
System™, refer to Section 5.4 for adjusting air-
2
System™, refer to section 5.5 for low KW heat air-
8
8
Above
15KW and
Model
15KW:
800 CFM
1200 CFM
1600 CFM
a
a
1800 CFM
below:
600 CFM
600 CFM
800 CFM
800 CFM
To adjust t
To adjust t