Cooling Delay Profiles; Cooling Mode Dehumidification - Passive - Rheem RH1V2417STANJA Installation Instructions Manual

Featuring industry standard r-410a refrigerant
Hide thumbs Also See for RH1V2417STANJA:
Table of Contents

Advertisement

FIGURE 27
FACTORY AIRFLOW SETTINGS FOR SWITCHES 5 AND 6 (-)H1V
5
6
5
6
O
O
O
N
N
N
A
B
SWITCH 5
SELECTION
POSITION
A
OFF
B
ON
C
OFF
D
ON
FIGURE 28
COOLING AIRFLOW ADJUSTMENTS (-)H1V
Advanced Cooling Adjustments
Switch 7 and 8 Settings and Characteristics
on
S7
off
S8
Moisture
Highest
Removal
5
6
5
6
O
N
C
D
SWITCH 6
(-)H1V-
POSITION
2417ST
OFF
800
OFF
600
ON
800
ON
600
5.6 COOLING DELAY PROFILES (-)H1V
The (-)H1V air handlers are shipped with a default 30 second blower OFF delay profile for
maximum efficiency.
IMPORTANT: Blower ON delay profiles are not used in heating mode.
5.7 COOLING MODE DEHUMIDIFICATION (-)H1V (PASSIVE: FACTORY
PROGRAMMED PROFILES)
Factory board settings will provide general overall performance under average conditions.
Use these Advanced Profiles to optimize performance and to add soft motor operation.
Please be sure that you check for correct airflow and adjust refrigerant charge based on your
Maximum Capacity and Airflow using the Factory AIRFLOW SETTINGS. Switches 1 and 2
should be set for the tonnage and airflow requirement for the system. Advanced Airflow set-
tings will, in most cases, greatly reduce airflow to the system and change the system's Latent
and Sensible capacity splits. The control board flashes CFM to the nearest 50 CFM calculat-
ed. We suggest that trouble-shooting be done with switches in the factory position for
verification of refrigerant charge and airflow through the duct system.
Factory
off
on
on
on
Good
Lowest
Standard
ELECTRIC HEAT AIR FLOW
(-)H1V-
(-)H1V-
3617ST
3821ST
1200
1200
600
600
1000
1000
600
600
off
off
TABLE 3 (-)H1V
S7
S8
On
Off
S7
S8
On Off
S7
S8
On
Off
MINIMUM AIR FLOW PER kW
3 kW to 13 kW
=
600 min. CFM
15 kW to 18 kW
=
800 min. CFM
20 kW to 25 kW
= 1400 min. CFM
30 kW
= 1800 min. CFM
(-)H1V-
(-)H1V-
4824ST
4824ST
1600
1800
800
800
1400
1600
800
800
Pre-programmed CFM Rates
Ramp Times
Operating
5 minutes
Sequence
5 to 12.5 minutes
after 12.5 minutes
Pre-programmed CFM Rates
Ramp Times
Operating
3 minutes
Sequence
3 to 8 minutes
after 8 minutes
Pre-programmed CFM Rates
Ramp Times
Operating
3 minutes
Sequence
after 3 minutes
(-)H1V-
6024ST
1800
800
1600
800
CFM Reduction
18% Less
12% Less
100% Full
CFM Reduction
25% Less
12% Less
100% Full
CFM Reduction
18% Less
100% Full
27