On Demand Dehumidification Airflow Adjustment - Active - Rheem RH1V2417STANJA Installation Instructions Manual

Featuring industry standard r-410a refrigerant
Hide thumbs Also See for RH1V2417STANJA:
Table of Contents

Advertisement

TABLE 4
SELECTION A EXPLANATION: MAXIMUM LATENT REMOVAL – PASSIVE (-)H1V
SWITCH POSITIONS
SWITCH 1
SWITCH 2
POSITION
POSITION
OFF
OFF
ON
OFF
OFF
ON
ON
ON
TABLE 5
SELECTION C EXPLANATION: ON DEMAND DEHUMIDIFICATION – ACTIVE (-)H1V
SWITCH POSITIONS
SWITCH 1
SWITCH 2
POSITION
POSITION
OFF
OFF
ON
OFF
OFF
ON
ON
ON
TABLE 6
ODD TERMINAL (-)H1V
INDOOR
INPUT TO "ODD"
AMBIENT
TERMINAL
CONDITION
(FROM HUMIDISTAT)
HIGH HUMIDITY
Ø V C
LOW HUMIDITY
24 V C
5.9 ON DEMAND DEHUMIDIFICATION AIRFLOW ADJUSTMENT – ACTIVE
(-)H1V
Use switches 9 & 10 to lower cooling airflow as defined in Figure 29:
FIGURE 29
ON DEMAND DEHUMIDIFICATION AIRFLOW ADJUSTMENT – ACTIVE (-)H1V
9 10
O
N
PASSIVE
SELECTION
PASSIVE
ACTIVE
IMPORTANT: Selection A turns off the input of the ODD terminal. DO NOT USE SELEC-
TION A WITH A DEHUMIDIFYING THERMOSTAT OR HUMIDISTAT (refer to Figure 29).
Selection C: On Demand Dehumidification (See Table 5) – Active
SWITCH 9
SWITCH 10
POSITION
POSITION
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
SWITCH 9
SWITCH 10
POSITION
POSITION
OFF
ON
OFF
ON
OFF
ON
OFF
ON
This selection allows On Demand Dehumidification when using a dehumidifying thermo-
stat or humidistat connected to the ODD wire (as shown in Figure 17). Nominal airflow is
reduced by a preprogrammed amount to maximize latent removal.
IMPORTANT: A humidistat or dehumidifying thermostat MUST be connected to the ODD ter-
minal when using this setting.
9 10
O
N
ACTIVE
SWITCH 9
SWITCH 10
POSITION
POSITION
OFF
OFF
OFF
ON
CABINET SIZE/COOLING CAPACITY
17/
17/
21/
1
1
& 2.0
2.0 & 3.0
3.0
2
680
1020
680
1020
510
850
510
850
CABINET SIZE/COOLING CAPACITY
17 / 2.0 & 3.0
ODD
1
17 / 1
/
& 2.0
2
INPUT
Y1 Y2
NONE
680
24V C
800
NONE
680
24V C
800
NONE
510
24V C
600
NONE
510
24V C
600
COOLING AIRFLOW ADJUSTMENT
MAXIMUM LATENT REMOVAL
(WITHOUT ODD INPUT)
ON DEMAND DEHUMIDIFICATION1
(WITH ODD INPUT)
CFM
21/
1
3
& 4.0
4.0 & 5.0
2
1360
1530
1360
1530
1190
1360
1190
1360
1
21 / 3
/
& 4.0
24 / 4.0 & 5.0
21/3.0
2
Y1 Y2
Y1 Y2
Y1 Y2
1020
1360
1530
1200
1600
1800
1020
1360
1530
1200
1600
1800
830
1190
1360
1000
1400
1600
830
1190
1360
1000
1400
1600
24/
29