be in the "configuration mode". While in this mode, the control display
will show the values of various configuration settings. The first setting to
be displayed is the "U1" setting. See setting summary. By using the in-
crease " ", decrease " " buttons, it is possible to scroll through the list
of settings to those needing modification.
To adjust a setting while in the "Configuration Mode", use the increase
" ", decrease " " buttons to bring the particular setting into the view
on the display. Press the "SET" button to change the value of the set-
ting. Once the "SET" button has been released, the display will flash.
Use the increase " ", decrease " " buttons to scroll through the op-
tions for the selected setting. After the option has been determined, press
the "SET" button once more to lock the new value into memory.
After completing all changes to the configuration of the control, the
new configuration must be saved. To save the new value, press the
increase " " and decrease " " buttons simultaneously. This will cause
the control to store the new values internally and then reset the unit.
Note: Switching off power to the unit before saving the new configura-
tion will cause all changes to be lost.

Main Menu Summary

Label Settings
U1
Sensor Type
U2
Signal Offset
U3*,** Output Signal Offset
U4
Signal Filter
U5
Set Point Dead Band (SP1)
U6
Set Point Dead Band (SP2)
U7
Power Save Set Point
U8
Display Stabilizer
L
Set Point Limit
F1
SP2 and U7 Disable
F2
Heat/Cool Switch
F3
Alarm Enable
F4
Unit Display Enable
F5
Temperature Unit
F6*
Current Output Enable
23
Description
Used to select the type of sensor
Offset -9 to +9 applied to reading
Adjusts 4-20 mA output from -9 to +9
Filter on input signals
Value from 1 to 99, SP1
Value from 1 to 99, SP2
Value from 1 to 99, power save mode
Stability when used with U4
High set point limit
Modifies control to single set point
N/A
Enable the "alarm set point"
Enable temperature units
Select ºF or ºC
Enable mA current
U1, Sensor Type
This setting tells the DQ15D control what type of sensor it is using.
Value
Board # Sensor Type
Sensor Description
1
5414
2-wire RTD
Platinum RTD, TCR 0.00385 ohm/ohm/ºC
2
5414
2-wire RTD
Platinum RTD, TCR 0.00392 ohm/ohm/ºC
3
5447*
3-wire RTD
Platinum RTD, TCR 0.00385 ohm/ohm/ºC
4
5447*
3-wire RTD
Platinum RTD, TCR 0.00392 ohm/ohm/ºC
5
5418** Thermocouple J-Type Iron-Constantan NIST Monograph
175 REV ITS-90
6
5418** Thermocouple K-Type Chromel-Alumel NIST Monograph
175 REV ITS-90
7
5418** Thermocouple T-Type Copper-Constantan NIST Monograph
175 REV ITS-90
8
5418** Thermocouple R-Type Platinum, 13% Rhodium-Platinum
NIST Monograph 175 REV ITS-90
9
5447*
Voltage
Potential signal (1.0 to 10.0 V)
10
5447*
Current
Current signal (4.00 to 20.00 mA)
11
5447*
Frequency
Pulse train frequency (0 to 200 Hz,
counts per second)
12
5447*
Resistance
Pure resistance signal (0 to 1000 ohms)
Note: The 5447 sensor board will also accept 2 wire RTDs. The default
sensor type setting is "1" (1000 ohm 2 wire RTD). When using the
5447 sensor board, an "on-board" DIP switch must also be config-
ured, see page 30.
* An optional 5416 sensor board will permit transmission of the pro-
cess value as a 4-20 mA signal.
** An optional 5419 sensor board will permit transmission of the pro-
cess value as 4-20 mA signal.
U2, Signal Offset
This setting, which may be any number from -9 to +9, represents an offset
value which is applied to the signal received from the sensor. The units
(ºC, ºF, ohms, etc.) will be dictated by the type of sensor selected in "U1"
settings.
24