Samsung AC071JXSCEH Installation Manual page 25

Hide thumbs Also See for AC071JXSCEH:
Table of Contents

Advertisement

Important information regulation regarding the refrigerant used
This product contains fluorinated greenhouse gases. Hermetically sealed system. Do not vent gases into the atmosphere.
Inform user if system contains 5 tCO2e or more of fluorinated greenhouse gases. In this case, it has to be checked
for leakage at least once every 12 months, according to regulation n°517/2014. This activity has to be covered by
CAUTION
qualified personnel only.
In case situation above (5 tCO2e or more of R-410A), installer (or recognised person which has responsability for
final check) has to provide a maintenance book, with all the information recorded according to REGULATION(EU)
N° 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on fluorinated greenhouse
gases.
Please fill in the following with indelible ink on the refrigerant charge label
supplied with this product and on this manual.
① : The factory refrigerant charge of the product.
② : The additional refrigerant amount charged in the field.
①+② The total refrigerant charge.
a. Factory refrigerant charge of the product: see unit name plate
b. Additional refrigerant amount charged in the field(Refer to the
NOTE
above information for the quantity of refrigerant replenishment.)
c. Total refrigerant charge
d. Refrigerant cylinder and manifold for charging
❋ The filled-out label must be adhered in the proximity of the product charging
port (e.g. onto the inside of the stop valve cover).
Pressure table for temperatures
If you need extra refrigerant charging due to leakage or relocating the product, refer to below table before charging
refrigerant.
AC071JXSCEH/EU
❋ Cooling operation
Outdoor Temp.(°C)
Indoor Temp.(°C)
(Dry-Bulb/Wet Bulb)
50
35
21
7
-18
Unit
①, a
②, b
①+②, c
Refrigerant type
R-410A
❋ GWP=Global Warming Potential
❋ Calculating tCO2e : kg x GWP /
1000
Indoor unit
32/23
27/19
1134
1020
1040
944
999
896
1020
912
1008
874
kg
tCO2e
GWP value
2088
d
Outdoor unit
Unit : [kPa, G]
21/15
916
777
802
808
766
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac100jxscghAc125jxscghAc100jxscehAc125jxscgh/eu

Table of Contents