Fluke 8600A Instruction Manual page 37

Table of Contents

Advertisement

8600A
c.
Short the V-£2
INPUT
terminal
HI
to
LO.
Select
the
200V
RANGE
and
VAC
FUNCTION.
d.
Connect
the return lead of the
test
equipment
voltmeter to the
8600A
V/ft
LO
input terminal.
e.
Connect
the high input lead
to
the ac converter
output
at
pin
9.
Note
the voltage
level.
f.
Move
the high input lead
to
pin
10.
The
voltage
level
should be
the
same
as
that
noted
in
step
e.
4-54.
A
difference
in
voltage
levels
between
the
two
pins
would
be
displayed
as
an
offset
on
the front panel
readout.
The
level at either
pin should
not exceed
+30
millivolts
nor be
less
than
+20
millivolt. If
the voltage
level
is
too high or
there
is
a
difference
in
voltage
level
between
the
two,
check
current source
CL1
or
transistors
Ql, Q7,
and Q9,
or capacitors
C12
and C13.
4-55.
The
operation of the
ac
converter with
an
ac
in-
put
applied,
observed
at
the
circuit
locations described
below,
may
indicate the
fault area.
With
the
8600A
in
the
2V
range
and
AC
V
function apply
a
IV
rms
500
Hz
signal
to the
V/£2
INPUT
terminals
and proceed
as
described
below.
a.
Connect
the input return lead
of an
oscilloscope
to
the
8600A
MA
LO
terminal.
b.
Connect
the scope input
probe
to
the ac convert-
er
input
at
the wire
connection
on S2A. Note
the
amplitude of
the
signal;
it
should be
2.8
volts
peak-to-peak.
c.
Move
the scope input
probe
to
U2
pin
6.
The
ac
signal at this
point should
be about
one-quarter
of
the
amplitude of
the
input
signal,
or
about
0.7
volts
peak-to-peak.
If
correct
go
to step
e.
d.
If
the
signal
is
not
present
at this
point or the
dc
voltage
level
is
close to either the
-1
5
volt
or
+
15
volt
supply,
U2, Q7,
or
CL1
are
probably
defective.
If
the
signal
is
distorted
check
the
operation of
Ql.
e.
Connect
the
scope input
probe
to the
base
of
Q7,
the
signal
here should be one-quarter
of
the
amp-
litude
of
the input
signal.
f.
The
ac converter
output
at
pin
9
should be
one
volt
dc
plus the
dc
voltage
offset
level
at
pin
10.
4-56.
A/D
CONVERTER OR CONTROL
AND
DISPLAY
4-57.
An A/D
converter or control
and
display
failure
will
generally affect
the operation
of
the
8600A
in
all
functions.
The
exceptions
to
this
would
be
a
malfunc-
tion
in
an
individual function's
control
signal
or
range
re-
lay
signal.
The
following
information
is
provided to
aid
in isolating
problems
within the
A/D
converter
and
control
and
display
circuitry.
4-58.
The
A/D
Converter can be
checked
by
using the
following procedure.
a.
Select the
DCV
function
and
the
2V
range.
b.
Apply
+1
V
dc
to
8600A
Vf2
terminals.
c.
Connect
the oscilloscope
probe
to
TP2.
The
probe
ground
return
may
be connected
to
TP3
or the
mA
LO
terminal.
d.
The
signal at
TP2
should be
as
shown
in
figure 4-3.
4-59.
The
stable
+5V
section
of
the
waveform shown
in
figure
4-3
should be
200msec
long
for a
+1
V
dc
input.
If
the
dc input
voltage
is
increased to
2V,
the
stable
portion
of
the
waveform
should be
300msec
long.
If
the
waveform
is
correct, the
problem
is
in
the display
section.
If
the
wave-
form
is
incorrect, refer to figure
44
for further
test
points
and waveforms
in
the
A/D
Converter.
Check
the
wave-
forms
at
the buffer,
U4,
for the correct voltage
from
Q14
and
the appropriate reference
(U17, Q17, and Q21).
U4
has
a
gain
of
5 so the
waveform
at
its
output should be
5
times
its
input (not
inverted).
The
output of
U5
should be
triangular as
shown
and
opposite
in
polarity to
the buffer
input.
Figure
4-3.
A/D
CONVERTER OUTPUT
SIGNAL
4-60.
The
control
waveforms and
timing
are
important
to the correct
operation of the
A/D
Converter.
The
wave-
forms and
test
points
are
shown
in figure
44.
Continue
with
the
test
setup
in
4-58.
First
check
the
signal at
the
gate
of
the
FET.
If
absent or
wrong, check
that
output
from U8,
keeping
in
mind
that the driver
transistors act as
inverters.
The
operation
of
U8
with
respect to the
A/D
Converter
may
be checked
as follows.
a.
Select
DCV
function
and
TV
range.
1/77
4-9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents