Page 2
PA3500/4200 Introduktionssidorna består huvudsakligen av bilder. För översättning av de engelska texter som används, se respektive språksidor. The introduction pages consist mainly of pictures. For translation of the English texts used, see the respective language pages. Introduksjonssidene består hovedsakelig av bilder. For oversettelse av de engelske tekstene, se de respektive språksidene.
Page 5
PA3500/4200 Fig. 1A: Open the unit by raising the front panel. Fig. 1B: When the front has been removed it it The front is blocked in open position with the important to be sure it is firmly seated in the front front hatch hook.
Page 10
PA3500/4200 Accessories Note! The air curtain must be secured in the wall or ceiling. PA3VDW PA4VDW PA3JK PA4JK Fig. 11: See separate manual for PA3JK / PA4JK.
Page 13
PA3500/4200 PA3500 A PA4200 A Transformer Transformer SIReB1 Actuator Supply 230V~ 230V~ ROOM...
Page 14
PA3500/4200 PA3500 E PA4200 E Transformer Transformer SIReB1 Actuator 230V~ ROOM...
Page 15
PA3500/4200 PA3500 W PA4200 W Transformer Transformer SIReB1 Actuator Supply 230V~ 230V~ ROOM...
Page 16
PA3500/4200 PA3500 E 230V3~ PA4200 E 230V3~ PA4210E/4215E PA4220E/4225E PA4215E/4220E/422 PA4210E °C °C °C °C White White Internal Motor protection sensor 230V Yellow 230V 200V Orange 200V 170V 170V 145V Brown 145V 120V Black 120V 100V Green 100V Blue Blue...
Page 17
PA3500/4200 SIReB Basic PA3500/4200 A PA3500/4200 E SIReUB1 SIReRTX SIReB1/B2/B1EC 230V~ (optional) ROOM Pot. Unit ID ACTUATOR SUPPLY SIReCC6XX L=2m (max 50 m) SIReCC6XX (max 10 m) SIReB1/B2/B1EC 230V~ ROOM Pot. Unit ID ACTUATOR SUPPLY SIReCC6XX (max 50 m) SIReB1/B2/B1EC...
Page 18
PA3500/4200 SIReB Basic PA3500/4200 W SIReUB1 SD230 SIReRTX SIReB1/B2/B1EC 230V~ (optional) ROOM Pot. Unit ID ACTUATOR SUPPLY SIReCC6XX L=2m (max 50 m) L=1,5m SIReCC6XX (max 10 m) SD230 SIReB1/B2/B1EC 230V~ ROOM Pot. Unit ID ACTUATOR SUPPLY SIReCC6XX (max 50 m)
Page 19
PA3500/4200 Technical specifications PA3500 Ambient, no heat - PA3500 A Type RSK-nr EL-nr Output Airflow* Sound Output Voltage Amperage Length Weight level* motor motor motor (SE) (NO) [kW] [dB(A)] [mm] [kg] PA3510A 673 53 66 49 320 44 0 860/1800...
Page 20
PA3500/4200 Technical specifications PA4200 Ambient, no heat - PA4200 A Type RSK-nr EL-nr Output Airflow* Sound Output Voltage Amperage Length Weight level* motor motor motor (SE) (NO) [kW] [dB(A)] [mm] [kg] PA4210A 673 53 70 49 320 48 0 1280/2700...
Page 21
PA3500/4200 Output charts water PA3500 WH Supply water temperature: 110 °C Water temperature: 110/80 °C Room temperature: +18 °C Room temperature: +18 °C Outlet air temperature: +35 °C* Type Airflow Output Return Water Pressure Output* Outlet Water Pressure position water temp.
Page 22
PA3500/4200 Output charts water PA3500 WL Supply water temperature: 80 °C Water temperature: 80/60 °C Room temperature: +18 °C Room temperature: +18 °C Outlet air temperature: +35 °C* Type Airflow Output Return Water Pressure Output* Outlet Water Pressure position water temp.
Page 23
PA3500/4200 Output charts water PA3500 WLL Supply water temperature: 55 °C Water temperature: 55/35 °C Room temperature: +18 °C Room temperature: +18 °C Outlet air temperature: +32 °C Type Airflow Output Return Water Pressure Output* Outlet Water Pressure position water temp.
Page 24
36,6 61,1 0,43 42,6 37,8 0,95 18,3 3020 17,4 47,8 0,12 26,7 44,0 0,59 ) Recommended outlet air temperature for good comfort and optimized output. ) Nominal output at given supply and return water temperature. See www.frico.se for additional calculations.
Page 25
35,7 0,46 18,5 35,8 34,7 0,43 16,7 3020 17,5 29,2 0,16 21,5 38,9 0,26 ) Recommended outlet air temperature for good comfort and optimized output. ) Nominal output at given supply and return water temperature. See www.frico.se for additional calculations.
Page 26
28,5 32,2 0,89 12,4 25,8 30,7 0,62 2820 13,2 31,8 0,28 14,4 33,1 0,35 ) Recommended outlet air temperature for good comfort and optimized output. ) Nominal output at given supply and return water temperature. See www.frico.se for additional calculations.
Page 27
Application area distance from outlet to floor for electrically heated units is 1800 mm. For other minimum PA3500 is intended for entrances and smaller distances, see fig. 3. doors up to 3.5 metres in height. PA4200 is intended for larger door ways and...
PA3500/4200 Vertical mounting PA3JK Unit with electrical heating The electrical connection is made on the Units from 1,5 metres and longer may be top of the unit (horizontal) or on the reverse used vertically. For vertical mounting, all (vertical). Control supply is 230V~ and cable...
Page 29
The connections to the heating coil must door. be equipped with shut off valves (included in Frico valve kits) to allow problem free removal. Filter (W) A vent valve should be connected at a high The water coil is protected against dirt and point in the pipe system.
PA3500/4200 Maintenance Temperature control Temperature control of SIRe maintains the Unit with water heating: exhaust temperature. If the temperature The appliance filter should be cleaned should exceed anyway the overheating alarm regularly to ensure the air curtain effect and goes off. For more information see the manual the heat emission from the device.
Page 31
PA3500/4200 Trouble shooting Safety • For all installations of electrically heated If the fans are not working or do not blow properly, products should a residual current circuit check the following: breaker 300 mA for fire protection be used. • That the intake grille/filter is not dirty.
Page 32
Main offi ce Frico AB Tel: +46 31 336 86 00 Box 102 SE-433 22 Partille mailbox@frico.se Sweden www.frico.se For latest updated information and information about your local contact: www.frico.se...