Diagnostics Using Alarm Number; Alarms; Faults - Siemens Micromaster Profibus Instruction Manual

Micromaster profibus optional board
Table of Contents

Advertisement

If alarms and faults occur on the PROFIBUS communication link, corresponding
alarm numbers are displayed on the converter (BOP/AOP).
Table 7-2
A700
A702
A703
A704
A705
A706
A710
A711
Table 7-3
A070
54
Alarm displays on converter
Cause:
The parameter or configuring settings by the PROFIBUS master are
invalid.
Remedy: Correct the PROFIBUS configuration
Cause:
The link to the PROFIBUS is interrupted.
Remedy: Check connector, cable and PROFIBUS master
Cause:
No setpoints, or invalid setpoints (control word = 0) are being
received from the PROFIBUS master
Remedy: Check setpoints from the PROFIBUS master. Switch SIMATIC CPU
to "RUN".
Cause:
At least one configured internode transmitter is not yet active, or has
failed.
Remedy: Activate internode transmitter.
Cause:
No actual values received from converter.
Remedy: None (fault is in converter)
Cause:
PROFIBUS-DP communication board: Software error.
Remedy: None (fault on the PROFIBUS-DP communication board, for details
see diagnostic parameter)
Cause:
Converter has detected failure of communication link to PROFIBUS-
DP communication board
Remedy: None (communication board may need to be replaced)
Cause:
Invalid value of a CB?? parameter.
Remedy: Check P0918 (PROFIBUS address) and P2041 (communication
board parameters)
Fault displays on converter
Cause:
No setpoints received from PROFIBUS-DP communication board.
Triggered by A702/A703/A704.
The telegram failure time set in P2040 has run out.
Remedy:
Check connection to communication partners and ensure valid
control word (see A702/A703/A704)