CONNECTIONS – PLUMBING
A disconnection union must always be provided at the cold water inlet,
solar cold water outlet, solar hot water inlet and hot water outlet on the
water heater to allow for disconnection of the water heater.
This water heater has either a plastic dip tube or fitting liner in the inlet
and outlet fittings (see diagram). These must be in place for the water
heater to function properly. Do not remove or damage them by using
heat nearby. They will be pushed into the correct position as the fitting
is screwed in.
PIPE SIZES
To achieve true mains pressure operation, the cold water line to the water heater should be the same size or
bigger than the hot water line from the water heater.
The pipe sizing for hot water supply systems should be carried out by persons competent to do so, choosing
the most suitable pipe size for each individual application. Reference to the technical specifications of the
water heater and local regulatory authority requirements must be made.
IN-SERIES BOOSTER (IF INSTALLED)
The pipe work between the solar storage tank and an in-series booster has a minimum recommended pipe
size of DN20, MUST BE of copper and be fully insulated with a closed cell type insulation or equivalent and in
accordance with the requirements of AS/NZS 3500.4. The insulation must be weatherproof and UV resistant
if exposed. The insulation must be fitted up to the connections on both the solar storage tank and the in-series
booster.
An isolation valve must be installed on the water line to the in-series booster. The isolation valve must be of a
full flow type if the in-series booster is a continuous flow water heater.
TEMPERATURE PRESSURE RELIEF VALVE
The temperature pressure relief valve is shipped either under the top flap of the water heater carton or behind
the front cover. The temperature pressure relief valve must be fitted before the water heater is operated. Before
fitting the relief valve, make sure the probe has not been bent. Seal the thread with an approved thread sealant
such as Teflon tape - never hemp. Make sure the tape does not hang over the end of the thread.
Screw the valve into the correct opening
(refer to the installation diagram on page 31)
leaving the valve outlet
pointing downwards. Do not use a wrench on the valve body - use the spanner flats provided. A copper drain
line must be fitted to the temperature pressure relief valve (refer to
"Relief Valve Drain"
on page 42).
The valve must be insulated with closed cell polymer insulation or similar (minimum thickness 9 mm) and the
insulation installed so as not to impede the operation of the valve. The insulation must be weatherproof and
UV resistant if exposed.
EXPANSION CONTROL VALVE
Local regulations may make it mandatory to install an expansion control valve (ECV) in the cold water line to
"Water
the water heater. In other areas, an ECV is required if the saturation index is greater than +0.4 (refer to
Supplies"
on page 16).
The expansion control valve must always be installed after the non-return valve and be the last valve installed
prior to the water heater
(refer to diagrams on page
40). A copper drain line must be fitted to the expansion
control valve (refer to
"Relief Valve Drain"
on page 42).
The valve, if installed within 500 mm of the water heater, must be insulated with closed cell polymer insulation
or similar (minimum thickness 9 mm) and the insulation installed so as not to impede the operation of the valve.
The insulation must be weatherproof and UV resistant if exposed.