Parameter Window "Controller Pwm Cooling - ABB i-bus KNX Product Manual

Room thermostat fan coil with display
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus KNX
3.2.7
Parameter window
"Control PWM cooling"
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Invert cooling
Options:
- Yes
- No
"Invert cooling" is used to adjust the direction of control action of the control
value to "de-energised open" or "de-energised closed" valves.
Cycle time PWM control value (min)
Options:
- 0 / 1 / 2 / ... / 10 / ... / 60
With PWM control, the actuator switches the valve drive depending on
the control value. The control thereby checks the "Cyclic time of the
switching control value".
Example: for a cyclic time of 10 min. and a control value of 60%, the valve
gear is switched on for 6 min. and off for 4 min.
Basically, the following applies for cyclic time: the more inactive the entire
system, the higher the cyclic time you can set.
This parameter is only available if the "Cooling" or "Heat and cool" control
functions are used and the cooling control type is set to "PWM".
36