Installation Procedure
CAUTION
Please do not install the unit in places where flammable gases may be leaked. In case that gas is leaked and accumulated
around the unit, it may cause dangers of fire etc.
The indoor unit shall be installed at locations where cold and hot air could evenly circulated. The following locations
should be avoided
Places with rich saline matters (seaside regions).
Places with plenty of gas sulfides (mainly in warm spring areas where the copper tube and braze weld is prone to corrosion).
Locations with much oil (including mechanical oil) and steam.
Locations using organic solvents.
Places where there are machines generating HF electromagnetic waves.
Positions adjacent to door or window in contact with high-humidity external air. (Easy to generate dew).
Locations frequently using special aerosols.
Selecting the mounting position to install the indoor units
Select suitable places where the outlet air can be sent to the entire room, and convenient to lay out
the connection pipe, connection wire and the drainage pipe to outdoor.
The ceiling structure must be strong enough to support the unit weight.
The connecting pipe, drain pipe and connection wire shall be able to go though the building wall
to connect between the indoor and outdoor units.
The connecting pipe between the indoor and outdoor units as well as the drain pipe shall be as
short as possible.
If it is necessary to adjust the filling amount of the refrigerant, please refer to the installation manual
attached with the outdoor unit.
The connecting flange should be provided by the user himself.
The indoor unit has two water outlets one of which is obstructed at the factory (with a rubber cap). Only the outlet not obstructed
(liquid inlet and outlet side) will be generally used during installation. If applicable, both the outlets should be used together.
An access port must be provided during installation of indoor unit for maintenance.
After selecting the unit installation location, proceed the following steps:
1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-through tube
purchased locally. The wall hole shall be with a outward down slope of at least 1/100.
2. Before drilling check that there is no pipe or reinforcing bar just behind the drilling position.
Drilling shall avoid at positions with electric wire or pipe.
3. Mount the unit on a strong and horizontal building roof. If the base is not firm, it will cause noise,
vibration or leakage.
4. Support the unit firmly.
5. Change the form of the connection pipe, connection wire and drain pipe so that they can go through the wall hole easily.
Installation dimension
Installation Procedure
Each of the air sending duct and air return duct shall be fixed on the prefabricated panel of the floor by the iron bracket. The
recommended distance between the edge of the air return duct and the wall is over 150mm.
The gradient of the condensate water pipe shall keep over 1%.
The condensate water pipe shall be thermal insulated.
When installing the ceiling Concealed type indoor unit, the air return duct must be designed and installed as figure shown.
Indoor unit dimensions(unit:mm)
Unit model
a
b
122
538
483.5
182, 242
1002
483.5
21
c
d
e
f
131
610
255
105
131
1105
255
105
Indoor Unit
g
h
i
418
508
220
880
970
220
Air Duct