PHYSICAL AND ELECTRICAL DATA

MODEL
Unit Supply Voltage
1
Normal Voltage Range
Minimum Circuit Ampacity
Max. Overcurrent Device Amps
Min. Overcurrent Device Amps
Compressor Type
Rated Load
Compressor
Amps
Locked Rotor
Crankcase Heater
Factory External Discharge Muffler
4
HS Kit Required with TXV
Fan Diameter Inches
Rated HP
Rated Load Amps
Fan Motor
Nominal RPM
Nominal CFM
Face Area Sq. Ft.
Coil
Rows Deep
Fins / Inch
Liquid Line Set OD (Field Installed)
Vapor Line Set OD (Field Installed)
6
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.
Operating Weight Lbs.
1. Rated in accordance with AHRI Standard 110-2012, utilization range "A".
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model.
5. For applications with non-standard vapor line sizes, see the "Applications & Accessories" section of this Technical Guide.
6. The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract
the amount of refrigerant, using the difference in actual lineset length (not equivalent length) multiplied by the per foot value.
A
Johnson Controls Unitary Products
YCS18B21S
YCS24B21S
11.8
13.6
2
20
20
3
15
15
Scroll
Scroll
9.0
10.2
56.3
61.6
No
No
No
No
No
No
18
22
1/12
1/8
0.64
0.80
1000
1075
1900
2875
12.37
13.83
1
1
23
23
3/8
3/8
5
3/4
3/4
3-6
3-12
0.62
0.62
130
135
C
B
A0339-001
YCS30B21S
YCS36B21S
208-230V, 1 60Hz
187 to 252
17.6
20.5
30
35
20
25
Scroll
Scroll
13.4
15.4
72.5
83.9
No
No
No
No
No
No
22
22
1/8
1/4
0.80
1.3
1075
850
2950
3275
13.83
17.37
1
1
23
23
3/8
3/8
3/4
3/4
3-15
4-10
0.62
0.62
140
155

DIMENSIONS

Unit
Model
A
YCS18B21S
33-1/4
YCS24B21S
30
YCS30B21S
30
YCS36B21S
36-1/4
YCS42B21S
33-1/4
YCS48B21S
33-1/4
YCS60B21S
36-1/4
‡ Adapter fitting must be field installed for the required 1-1/8" line set.
All dimensions are in inches and are subject to change without notice.
Overall height is from bottom of base pan to top of fan guard.
Overall length and width include screw heads.
5006080-YTG-B-1215
YCS42B21S
YCS48B21S
22.1
25.7
35
45
25
30
Scroll
Scroll
16.6
19.5
109.0
130.0
No
No
No
No
No
No
24
24
1/4
1/4
1.3
1.3
850
850
3500
3500
18.74
18.74
1
1
23
23
3/8
3/8
7/8
7/8
4-15
4 - 15
0.67
0.67
200
200
Dimensions
Refrigerant Connection
(Inches)
Service Valve Size
B
C
Liquid
24
24
29-1/4
29-1/4
29-1/4
29-1/4
29-1/4
29-1/4
3/8
35-1/4
31-3/4
35-1/4
31-3/4
38
34-1/4
YCS60B21S
31.7
50
35
Scroll
24.3
144.2
No
No
No
26
1/4
1.3
850
4300
23.40
1
23
3/8
1-1/8
5 - 12
0.75
205
Vapor
3/4
7/8
7/8
3

Advertisement

Table of Contents