Fujitsu AB*G14LVTA Service Instructions Manual page 63

Universal floor / ceiling slim duct / compact cassette compact wall mounted / wall mounted / floor inverter multi
Hide thumbs Also See for AB*G14LVTA:
Table of Contents

Advertisement

Trouble shooting 23
OUTDOOR UNIT Error Method:
Heat sink thermistor error
Detective Actuators:
Outdoor unit Main PCB
Heat sink temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature(°C)
Resistance Value (k )
Temperature(°C)
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
1 2
1 2
CN25
CN26
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When the heat sink temperature thermistor open or short-circuit is
detected at power ON or while running the compressor.
2.Thermistor failure
-30
-20
-10
92.3
49.2
27.5
50
60
70
1.8
1.2
0.9
1 2
1 2
1 2
CN23
CN22
CN21
02-26
3. Main PCB failure
0
10
20
16.1
9.7
6.1
80
90
100
0.6
0.5
0.4
30
40
3.9
2.6