Fujitsu AB*G14LVTA Service Instructions Manual page 51

Universal floor / ceiling slim duct / compact cassette compact wall mounted / wall mounted / floor inverter multi
Hide thumbs Also See for AB*G14LVTA:
Table of Contents

Advertisement

Trouble shooting 11
INDOOR UNIT Error Method:
Damper(Open/Close) detection
limit switch error
Detective Actuators:
Indoor unit Controller PCB
Limit switch
Damper
Forecast of Cause :
1. Limit switch failure
4. Controller PCB failure
Check Point 1 : Check Limit switch
Check operation of limit switch. (any blocking by dust, etc.)
Remove Limit switch and check ON/OFF switching operation by using a meter.
>>If Limit switch is detective, replace it.
OK
OK
Check Point 2 : Check Connector (CN18) / Wire
Check Point 2 :
Check loose contact of CN18 /shorted wire (pinched wire).
>>Replace Limit switch if the wire is abnormal
OK
OK
Check Point 2 :
Check Point 3 : Check Damper
Check the obstruction of damper movement.
Check the damper movement.
>>Replace Damper if the damper is abnormal
OK
OK
Check Point 4 : Replace Controller PCB
If Check Point 1
3 do not improve the symptom, change Controller PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When limit switch were not able to detect the close though the damper close.
(Upper air flow)
When limit switch were not able to detect the open though the damper open.
(Upper & Lower air flow)
2. Shorted connector/ wire
02-14
3. Damper faulure