2.11 Self Monitoring

The relay incorporates a number of self-monitoring features. Each of these features can initiate a controlled reset
recovery sequence.
Supervision includes a power supply watchdog, code execution watchdog, memory checks by checksum and
processor/ADC health checks. When all checks indicate the relay is operating correctly the 'Protection Healthy'
LED is illuminated.
If an internal failure is detected, a message will be displayed. The relay will reset in an attempt to rectify the
failure. This will result in de-energisation of any binary output mapped to 'protection healthy' and flashing of the
protection healthy LED. If a successful reset is achieved by the relay the LED and output contact will revert back
to normal operational mode, and the relay will restart, therefore ensuring the circuit is protected for the maximum
time.
A Start-up Counter Meter is provided to display the number of start-ups the relay has performed. Once the
number of start-ups has exceeded a set number, an Alarm output can be given.
Reset of the counter can be done from the meter or via a binary input or a command.
Various types of start-up are monitored by the relay:
1. power-on starts
2. expected starts (user initiated via comms)
3. unexpected starts (caused by the relay watchdog)
Any combination of these can be selected for the start-up count. This is done in the MAINTENANCE
MENU>START COUNT menu using the Start Up Types setting. All the start-up types selected (ticked) will be
added to the overall start-up count.
The number of restarts before the alarm output is raised is set in the MAINTENANCE MENU>START COUNT
menu using the Start Up Count Target setting.
When the number of relay start-ups reaches the target value an output is raised, OUTPUT MATRIX>Start Up
Count Alarm, which can be programmed to any combination of binary outputs, LED's or virtual outputs.
The following screen-shot shows the events which are generated when the relay re-starts. The highlighted events
show the cause of the re-start. The event which comes next shows the type of restart followed by the relay:
Warm, Cold or Re-Start.

2.11.1 Protection Healthy/Defective

When the relay has an auxiliary DC supply and it has successfully passed its self-checking procedure then the
front facia Protection Healthy LED is turned on.
A changeover or open contact can be mapped via the binary output matrix to provide an external protection
healthy signal.
A changeover or closed contact can be mapped via the binary output matrix to provide an external protection
defective signal. With the 'Protection Healthy' this contact is open. When the auxiliary DC supply is not applied to
the relay or a problem is detected within the relay then this output contact closes to provide external indication.
If the relay is withdrawn from the case, the case shorting contact will make across the normally closed contacts to
provide and external alarm.
©2012 Siemens Protection Devices Limited
--------------------
|Start Alarm
|Count
|Target
|
--------------------

Figure 1-22 Start-up Counter Meter

7SR11 & 7SR12 Description Of Operation
|