7SR21 & 7SR22 Argus Installation Guide
6.3

Additional (Optional) Fibre Optic Connections

Rear Com ports 3 and 4 comprise Fibre–Optic ST™ (BFOC/2.5) bayonet connectors-4 per product. 62.5 / 125μm
glass fibre is recommended for all distances.
When installing fibre, ensure that the fibres' bend radii comply with the recommended minimum for the fibre used-
typically 50mm is acceptable.

Figure 6.3-1 Data Comms to Multiple Devices Using 7SG24 and F.O. Star Network

Figure 6.3-2 Data Comms to Multiple Devices Using 7SG24 and F.O. Ring Network

The F.O. data communications link with a particular relay will be broken if the relay element is withdrawn from the
case, all other relays will still communicate.