6-2-9. Operating Rate Output

Header outdoor unit
Operation
At the output terminals, a signal is present (relay closed) or absent (relay open) in various combinations according
to the system operation factor, as shown in the diagram.
The operation rate (FA) is the percentage ratio of the current output of the system to the maximum output (100%).
Function
SW16
System operation
ON
rate output
OFF
Bit 1: ON
Bit 2: OFF
off = Relay open
on = Relay closed
C2
Connector cable 2 ( 2 )
CN514
Connector on interface side (green)
K1, K2, K3
Relays
MONITOR
Monitoring device
Output terminal for each function
OUTPUT1
Output terminal for each function
OUTPUT2
Output terminal for each function
OUTPUT3
PJ20
Connector on optional PCB side
TB1
Terminal block
* Connect the optional P.C. board to the header outdoor unit.
Note 1: Output Relay (K1, K2, K3) Contact Specifications
• Output terminals (OUTPUT1, 2, 3) must satisfy the following electrical rating.
• When connecting a conductive load (e.g. relay coil) to loads K1, K2 and K3, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
<Electrical Rating>
220-240 VAC, 10 mA or more, 1A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
Optional PCB
Outdoor unit
interface PCB
C2
SW16
PJ20
ON
CN514
OFF
1 2 3 4
OUTPUT1
off
on
1
2 3 4
off
on
off
on
off
on
Locally procured
(See "NOTE")
TB1
1
K1
OUTPUT1
2
3
K2
OUTPUT2
4
5
K3
OUTPUT3
6
Shield
wire
OUTPUT2
OUTPUT3
off
off
off
off
on
off
on
off
off
on
off
on
on
on
on
on
− 79 −
MONITOR
Operation factor (FA)
FA=0%
<
<
0%
FA
20%
20% FA
<
35%
<
35% FA
50%
<
50% FA
65%
<
65% FA
80%
<
80% FA
95%
95% FA