Decommissioning

What this chapter contains

This chapter explains how to remove the inverter from service and recycle it at the
end of its lifetime.

Removing the inverter from service

1. Switch OFF the DC switch on the front panel of inverter.
2. Electrically isolate the inverter. See
power sources
3. Turn off all disconnecting switches and circuit breakers on the DC side.
4. Turn off the disconnecting switches and circuit breakers at the AC distribution
board.
5. Remove the front and bottom covers. See
and bottom cover
6. Disconnect the AC cable connector.
7. Disconnect the DC cable connectors.
8. Disconnect auxiliary power cables (if applicable). The power supply from the
external control equipment must be disconnected either with applied circuit
breaker or power switch.
9. Disconnect control cables. The power supply from the external control equipment
must be disconnected either with applied circuit breaker or power switch.
10. Ensure that disconnected cables are not left in a hazardous state.
11. Remove protective earthing connections (if applicable).
on page 11.
on page 41.
Isolating the PVS300 inverter from external
Removing and replacing the front cover
Decommissioning 99