Process Station
Cold start
stopped
Warm start
stopped
Starting
Running
Running partially
Version error,
running
[del2]
Wrong
station number
Incompatible
EPROM version
Gross Automation, 1725 South Johnson Road, New Berlin, WI 53146, www.ssacsales.com, 800-349-5827
36
The command to cold start the resource had been initiated by the person
responsible for commissioning, or from the system function „Force cold
start". Indicates self-test of the FieldController was OK, however, the
RUN/STOP switch on the FieldController was in the STOP position or the
resource was stopped by the person responsible for commissioning before
achieving running state.
The cold start task, Name.ColdSt (where Name = resource name)
is executed only when the resource is started (STOP to RUN).
When cold starting, all the resource data is initialized. The operat-
ing system is not affected and the output module channels assume
their safety values.
The command to warm start the resource was initiated by the person re-
sponsible for commissioning or a power failure (power-fail signal from the
power supply unit), the RUN/STOP switch on the FieldController was set to
STOP or the resource was stopped before achieving running state by the
person responsible for commissioning.
The warm start task, Name.WarmSt (where Name = resource
name) is executed only when the resource is started (STOP to
RUN). When warm starting, all data and variable values of the re-
source are unaffected and the output module channels assume
their safety values.
Resource in transition from stopped to running
This state is only displayed if task processing takes a relatively
long time.
Resource started and RUN/STOP switch in RUN position
Not all resource program objects are processing, e.g. task in stop or pro-
gram list OFF
There are user program version disparities between the active station and
the assigned resource. Such disparities are displayed independently of the
run state of the resource, and are therefore also displayed when stopped.
Resource objects have been deleted, in this case, two objects
The station number in the FieldController does not match the station num-
ber in the hardware structure (network).
The EPROM version of the CPU module or FieldController does not match
the software version of the engineering software.
The boot EPROM must be updated. See Engineering Manual,
System Configuration, Installation DigiTool.
ABB FieldController 800