FP-X series
Specifications
General specifications
Item
Rated voltage
100 to 240VAC (AC power), 24VDC (DC power)
85 to 264VAC (AC power), 20.4 to 28.8VDC (DC power)
Operating voltage range
C14: 24VDC/0.15A, C30 and C60: 24VDC/0.4A
Service power output
40A or less (C14), 45A or less (C30, C60) at 25°C (AC power)
Rush current
12A or less at 25°C (DC power)
Allowed momentary power off time
110ms or more
0 to +55°C
Ambient temperature
-40 to +70°C
Storage temperature
Ambient humidity
10 to 95% RH (at 25°C, non-condensing)
Storage humidity
10 to 95% RH (at 25°C, non-condensing)
Combined input/output terminals - Combined power and ground terminals,
1
2300VAC*
1 minute (AC power), 500VAC*
Input terminals - Relay output terminals, 2300VAC*
Breakdown voltage
Input terminals - Transistor output terminals, 500VAC*
Power terminals - Ground terminals, 1500VAC*
500VAC *
1
1 minute (DC power)
Combined input/output terminals - Combined power and ground terminals,
100M or higher (500VDC using an insulation resistance meter)
Insulation resistance
Input terminals - Output terminals, 100M or higher (500VDC using an insulation resistance meter)
Power terminals - Ground terminals, 100M or higher (500VDC using an insulation resistance meter)
5 to 9Hz, single amplitude 3.5mm/9 to 150Hz, constant acceleration 9.8m/s
Vibration resistance
1 sweep/min, 10 sweeps in each XYZ direction
2
147m/s
, 4 times on 3 axes
Shock resistance
1500V [P-P] pulse width 50ns, 1 s (AC power),
500V [P-P] pulse width 50ns, 1 s (DC power)
Noise immunity
(per noise simulator method) (power terminals)
Operating condition
No corrosive gas and no excessive dust
EC Directive Compliance Standard
Conforming to EN61131-2
Level of contamination
2
Over-voltage category
II
Note:
*1
Cutoff current 5mA
20
Description
1
1 minute (DC power)
1
1 minute
1
1 minute
1 minute (AC power),
1
2
,
Power consumption, weight
Product name
Part number
AFPX-C14
Control Unit
AFPX-C30
AFPX-C60
AFPX-E16
Expansion I/O Unit
AFPX-E30
Expansion FP0 adapter
AFPX-EFP0
Input cassette
AFPX-TR8
Output cassette
AFPX-TR6P
Pulse I/O cassette
AFPX-PLS
Master memory cassette
AFPX-MRTC
Analog input cassette
AFPX-AD2
Analog I/O cassette
Analog output cassette
AFPX-DA2
Thermocouple input cassette
AFPX-TC2
AFPX-COM1
AFPX-COM2
Communication
AFPX-COM3
cassettes
AFPX-COM4
AFPX-COM5
AFPX-COM6
Notes:
*2
Power consumption by the AC power supply connected to the control unit
*3
Power consumption by the DC power supply connected to the expansion FP0 adapter
Please refer to the user manual and specifications for further details.
01/2008
Current consumption
26W or less*
2
Approx. 280g or less
52W or less*
2
Approx. 490g or less
64W or less*
2
Approx. 780g or less
8W or less*
2
Approx. 195g or less
2
Approx. 470g or less
45W or less*
3
0.24W or less*
AFPX-IN8
1W or less*
2
1W or less*
2
1W or less*
2
2W or less*
2
2W or less*
2
2W or less*
2
AFPX-A21
3W or less*
2
2
5W or less*
2
1W or less*
2W or less*
2
2
3W or less*
2W or less*
2
Weight
Approx. 65g
Approx. 25g
Approx. 25g
Approx. 25g
Approx. 25g
Approx. 20g
Approx. 25g
Approx. 25g
Approx. 25g
Approx. 25g
Approx. 20g
Approx. 25g
Approx. 20g
Need help?
Do you have a question about the Programmable Controllers FP-X Series and is the answer not in the manual?
Questions and answers