FP-X series
Network
Different types of equipment need to be linked – FP-X flexibly meet such requirements.
Up to 3 serial communication ports can be used simultaneously
Usable interfaces include RS232C, RS485, RS422 and USB.
* The RS232C tool port can be used as a general-purpose serial communication port.
COM1: RS232C, RS485, Ethernet
COM2: RS232C, RS485, USB (The cassette port and the USB port cannot be used simultaneously.)
Tool port: RS232C
PLC link (MEWNET-W0)
Bit data/word data can be shared (linked) among up to 16 FP-X units. This is ideal for linking adjacent equipment in a distributed
control system.
Links with our other PLCs (FPS (Sigma), FP2/FP2SH) are possible.
Simple setting of the number of linked units, linked relays
and starting area address of the own station by using FPWINPro
allows contact information and data to be shared without program-
ming.
Baud rate of 115.2kbps, the highest rate for a compact model.
A transfer distance of 1200m, the longest distance for a
compact model.
FP-X and FPS (Sigma) allow a change of the station number by
programming (SYS instruction).
FP-X requires a communication cassette (AFPX-COM3, AFPX-COM4 or AFPX-COM6)
FP2/FP2SH requires a multi-communication unit (FP2-MCU, FP2-CB485)
FPS (Sigma) requires a communication cassette (FPG-COM3-A, FPG-COM4-A)
Modbus-RTU compatibility
Compatible with both the master and slave of the Modbus RTU, the world's de-facto standard. Great performance is expected for air-
conditioning, temperature control, etc.
Usable as a master station [F145 (SEND), F146 (RECV) commands]
Capable of easily communicating with a temperature controller, inverter, FP-e and foreign PLC
Temperature
Watt-hour meter
controller
Another available application
When 17 or more FP-X units need to be linked, the use of Modbus in-
stead of MEWNET-W0 (see above) can accommodate up to 99 FP-X
units. Because each FP-X can be a master or a slave, a multi-master link
can be constructed by passing a token from a user program.
Communication cassette (two-channel type)
AFPX-COM2 (RS232C + RS232C)
AFPX-COM4 (RS485 + RS232C)
AFPX-COM5 (Ethernet + RS232C)
AFPX-COM6 (RS485 + RS485)
Inverter
FP2
FP-e
01/2008
Item
Number of stations
Transmission speed
Transmission distance
Shared data
Communication method
16 stations, 115.2 kbps, 1200m
RS485
Can also be used as
a slave station
FP (Sigma)
Token passing (by user program)
Master/
Master/
Master/
slave
slave
slave
Specifications
16 stations
115.2kbps
1200m
128 words (data register),
64 words (contacts)
Floating master
Twisted-pair cable
Multi-master link of up
Master/
to 99 units is possible.
slave
13