Controller; Par-W21Maa Specifi Cations - Mitsubishi Electric PWFY-P200VM-E-AU Data Book

Hide thumbs Also See for PWFY-P200VM-E-AU:
Table of Contents

Advertisement

Controller

VI
1. PAR-W21MAA specifi cations
Item
ON/OFF
Operation mode switching
Water temperature setting
Preset temperature range
Water temperature display
Permit / Prohibit
local operation
Weekly scheduler
Error
Self check (Error history)
Test run
Circulating water
replacement warning
LANGUAGE setting
Operation locking function
Runs and stops the operation of a group of units
Switches between Hot Water / Heating / Heating ECO / Anti-freeze / Cooling
*
Available operation modes vary depending on the unit to be connected.
*
Switching limit setting can be made via a remote controller.
Temperature can be set within the ranges below. (in increments of 1°C or 1°F)
Hot Water
30°C ~ 70°C
Heating
30°C ~ 45°C
Heating ECO 30°C ~ 45°C
Anti-freeze
10°C ~ 45°C
Cooling
10°C ~ 30°C
*
The settable range varies depending on the unit to be connected.
Preset temperature range setting can be limited via a remote controller.
10°C ~ 90°C
(in increments of 1°C or 1°F)
*
The settable range varies depending on the unit to be connected.
Individually prohibits operations of each local remote control function :ON/OFF,
Operation modes,water temperature setting, Circulating water replacement
warning reset.
*
Upper level controller may not be connected depending on the unit to be connected.
ON / OFF / Water temperature setting can be done up to 6 times one day in the week.
(in increments of a minute)
When an error is currently occurring on a unit, the afflicted unit and the error code
are displayed.
Searches the latest error history by pressing the CHECK button twice.
Enables the Test run mode by pressing the TEST button twice.
*
Test run mode is not available depending on the unit to be connected.
Displays the circulating water replacement warning via the unit message.
Clears the display by pressing the CIR.WATER button twice.
*
Circulating water replacement warning is not available depending on the unit to
be connected.
The language on the dot matrix LCD can be changed. (Seven languages)
English/German/Spanish/Russian/Italian/French/Swedish
Remote controller operation can be locked or unlocked.
·All-switch locking
·Locking except ON/OFF switch
Description
- 67 -
Operations Display

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pwfy-p100vm-e-auPwfy-p100vm-e-bu

Table of Contents