(2)-5-2 Heating capacity correction
PQRY-P200YHM-A
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
Piping equivalent length (m)
PQRY-P250, 300YHM-A
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
Piping equivalent length (m)
(2)-5-3 How to obtain the equivalent piping length
1 PQRY-P200YHM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bends in the piping) m
2 PQRY-P250, 300YHM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bends in the piping) m
3 PQRY-P400, 450, 500, 550, 600YSHM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bends in the piping) m
(2)-5-4 Correction by port counts of the BC controller
Indoor unit sizes P200 and P250 must be connected to 2 ports on the BC controller.
Indoor unit sizes from P100 to P140 should normally be connected to 2 ports on the BC controller (set BC controller
DIP-SW 4-6 to its ON position).
In cases whereby indoor unit sizes from P100 to P140 are connected to only 1port on the BC controller (set BC controller
DIP-SW 4-6 to its OFF position), the cooling capacity of the indoor unit should be multiplied by a correction factor of
0.97.
80
100
120
140
160
180
80
100
120
140
160
180
PQRY-P400, 450, 500YSHM-A
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
Piping equivalent length (m)
PQRY-P550, 600YSHM-A
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
Piping equivalent length (m)
- 108 -
80
100 120 140 160 180
80
100
120
140
160
180