Start-Up Procedure; Check Water Piping; Check Gas Piping; Check Operation - PEERLESS PUREFIRE PFW-399 Installation, Operation & Maintenance Manual

Gas hot water supply boilers pfw series
Hide thumbs Also See for PUREFIRE PFW-399:
Table of Contents

Advertisement

9. START-UP PROCEDURE

A. GENERAL
1. Confirm that all water, gas and electricity are turned off.
2. Verify that the water piping, venting & air intake
piping, gas piping, electrical wiring and electrical
components are installed in accordance with the
manufacturer's instructions. Be sure that the boiler is
installed in accordance with this manual and good
engineering practice.
3. Turn on electricity and gas to the boiler
B. CHECK WATER PIPING
1. Fill the boiler and system with water, making certain
to purge all air from the system. Open each vent in
the system until all air is released and water begins to
be discharged. Then close the vent.
2. The pressure reducing valve on the fill line will
typically allow the system to be pressurized to 12 PSI.
Consult manufacturers instructions for operation of
the valve and expansion tank.
3. Check joints and fittings throughout the system and
repair as required.
C. CHECK GAS PIPING
1. Turn on gas to the boiler using the shut-off valve
upstream of the sediment trap. Be sure that the gas
shut-off valve supplied with the boiler is in the closed
position.
2. Connect a manometer to the gas supply upstream of
the supplied manual gas valve.
3. Confirm that the gas supply pressure to the boiler is
between the minimum and maximum values as
indicated in Section 5.
4. If a supply pressure check is required, isolate the
boiler and gas valve before performing the pressure
test. If the supply pressure is too high or too low,
contact the fuel gas supplier.
5. Double check the fuel gas supply pressure after the
boiler is running to be sure that the pressure doesn't
drop off significantly under operation.
D. CHECK OPERATION
1. Be sure that the circuit between terminals #1 & #2 is
open to disable boiler operation.
2. Turn on electricity to the boiler leaving the manual gas
valves closed. Check to see that LCD display is lit.
Figure 9.1 shows the status display.
Figure 9.1:
Status Display DHW Disabled
3. Refer to Section 8, Boiler Control, to set up the
control for the desired operation.
4. Close terminal #1 & #2 either with a switch or jumper
to enable boiler operation. Before opening the gas
valves, allow the boiler to attempt ignition 3 times
before locking out on Ignition Failure (A01). Then turn
the manual gas valves on and push the Reset key.
5. Use the ignition sequence, Figure 8.1 to follow the
light off and shutdown sequences and to assist in
troubleshooting operation problems. If the boiler does
not function properly, consult Section 10,
Troubleshooting.
6. After starting the boiler, be certain that all controls are
working properly and that the combustion is properly
set up. Paragraphs 7 and 8 below provide instructions
on how check combustion.
7. Check that the boiler will shut down when the supply
water temperature reaches the control setpoint.
a. Note the boiler setpoint by accessing the User
Menu, Status Display. Press the Menu key on the
keypad. Choose Status by pressing the Select
Þ
key. Use the
available parameters. Refer to Section 8.B for
information on User Menu options.
b. Use the System Test Mode in the Installer Menu to
choose High Input Power.
c. Monitor the boiler temperature on the temperature
gauge (supplied for field mounting) and on the
Status display.
d. The boiler should shut down at the boiler setpoint
plus 10°F (5°C). If it does not shut down, turn off
the boiler and contact your PB Heat representative.
8. Check combustion readings in the boiler vent pipe.
a. For PVC or CPVC exhaust vent pipe only: Drill
and tap a 1/8" NPT threaded hole in the boiler
vent pipe within 12" (305 mm) of the boiler vent
connection. (21/64" Drill and 1/8" NPT Pipe Tap
recommended) This is to be used as the
combustion test port for the combustion analyzer.
See Figure 9.2.
b. Polypropylene vent systems from Centrotherm or
Duravent should include a sample port fitting
connected to the exhaust outlet port of the boiler.
In this case, this fitting is to be used as the test
port for the combustion analyzer.
START-UP PROCEDURE