Functions
8.17 Diagnostics functions
Diagnostic warning
Measured value out of the measurement
area
Output saturation warning
Measured value (PV) outside the sensor
limit
Electronics temperature outside the limit
1)
2)
Note
• The configuration will not be completely stored in the device if the supply voltage fails
• The transmitter detects a defective device configuration and signals this by the red
• The specification of the transmitter is no longer guaranteed if the device detects that it
• The SIPROM T or SIMATIC PDM parameterization software can be used to reset the
• Even after recalibration, devices approved for explosion protection may no longer be
52
A diagnostic interrupt is not triggered unless the measured value is higher or lower than the
limit value by 3 °C (5.40°F).
A diagnostic warning is triggered immediately when the measured value exceeds the limit
value. The diagnostic interrupt is triggered in any case if the limit value is exceeded by more
than 2%.
during a write operation to the device. In this case, a new configuration must be written to
the device. The device will then revert to working in accordance with the specifications.
diagnostic LED being continuously lit. In this case, HART additionally sets the "HW/FW
error" diagnostic bit.
CAUTION
has been exposed to temperatures beyond its ambient temperature limits (-40 °C to
+85 °C). In this case, the transmitter outputs the fault current set in its parameters as the
output signal. The "Ambient temperature error/electronics temperature error" flag
remains set in the device even after the power supply has been switched off and on
again.
"Ambient temperature error/electronics temperature error" flag within the device.
– SIPROM T menu item for SITRANS TR200:
Device ➜ Device status ➜ Device reset after ambient temperature error
– SIMATIC PDM menu item for SITRANS TR300:
View ➜ Device status ➜ Device reset after ambient temperature error
The rest can only be performed if it has been ensured by sensor trim and D/A trim
that the transmitter is operating within the user's accuracy tolerances.
used in explosion-protected environments.
Status
Unchanged
Status
Unchanged
Status
Unchanged
Status
Unchanged
Operating Instructions, 04/2007, A5E01071992-01
Green
Green
Green
Green
SITRANS TR200/TR300