Fig. 35: Gas Valve Adjustment (Invensys Valve)
8. Carefully place the spring & weight back in before
replacing LO-fire adjustment cap.
9. For LO-fire adjustment, tighten the cap to increase
the pressure, loosen to decrease.
10. When correct settings are set, replace the sole-
noid and tamper screw in place.
Gas Type Conversion on Valve
WARNING: Burner orifices must be changed when
changing gas type.
NOTE: Model HD401 requires replacement of
valve.
1. Turn off gas supply at the appliance service level.
2. Remove the pressure regulator cover assembly.
3. Remove the existing stem/spring assembly.
4. Insert the replacement stem/spring assembly.
5. Replace the pressure regulator cover assembly
and tighten screws.
6. Mount conversion labels on the gas valve.
Fig. 36: Gas Type Conversion on Honeywell Valve
Safety Inspection
•
Replace main gas manifold adjustment screw cap.
•
Check all thermostats and high limit settings.
•
During the following safety checks leave manome-
ters hooked up, check and record.
•
If other gas fired equipment are in the room and on
same gas main check all pressures on the Hi Delta
SS with all other equipment running.
•
Check thermostats for ON/OFF operation.
•
Check High limits for ON/OFF operation.
•
While in operation, check flow switch operation.
•
Check the low gas pressure switches (For proper
adjustment, if available, use the attached
manometers to set pressure. The scales on the
switch are approximate only); Low gas pressure
switch (optional) must be set at 3.5 in. WC for nat-
ural gas and 10.5 in. WC for LP gas.
•
High gas pressure switch (optional) at 1 in. WC
above manifold pressure.
•
Insert ignition control lockout tests as safety
check.
Follow-Up
•
Safety checks must be recorded as performed.
•
Turn unit on.
After main burner ignition:
•
Check Manometer(s) for proper reading(s).
•
Cycle unit several times and recheck readings.
•
Re-analyze with unit running record or print
results.
44