Outdoor Unit Installation Guidelines
• Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.

10.2. Install The Outdoor Unit

• After selecting the best location, start installation to Indoor/
Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and
horizontally by bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and
earthquake.
Please fasten the installation stand firmly with bolt or
nails.

10.3. Connect The Piping

• Remove the control board cover (resin) from the unit by
loosening three screws
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge. Make flare after inserting the
flare nut (locate at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque
wrench to the specified torque as stated in the table.
Model
A
CU-3E18***
613 mm
CU-4E23***
Piping size
1/4" [6.35 N
m]
3/8" [9.52 N
m]
1/2" [12.7 N
m]
5/8" [15.88 N
m]
3/4" [19.05 N
m]
Do not over tighten, over tightening cause gas leakage.
29
B
C
131 mm
16 mm
360.5 mm
Torque
[18 N
m (1.8 kgf.m)]
[42 N
m (4.3 kgf.m)]
[55 N
m (5.6 kgf.m)]
[65 N
m (6.6 kgf.m)]
[100 N
m (10.2 kgf.m)]
D