[5].INSTALLATION DIMENSION OF INDOOR UNIT
Outline of indoor unit
[6].INSTALLATION PROCEDURE
1
PLACING THE MOUNTING PLATE AND MAKING A PIPING HOLE
Installing the mounting plate
‡ The mounting plate should be installed on a wall which can support the weight
of the indoor unit.
(1)
the piping hole.
‡ 0DNH VXUH WKDW WKH PRXQWLQJ SODWH LV KRUL]RQWDOOy.
(2) Secure the mounting plate to the wall with the long screws and
FKHFN WKH VWLffness.
2
CONNECTING THE CABLE TO THE INDOOR UNIT
Connecting wires and the ground wire
‡ Use solid conductor A:* RU VWUDQGHG FRQGXFWRU A:*  A:* RU ODUJHU
if required by local electrical code)
‡ Use double insulated copper wire with 600 V insulation.
‡ Use copper conductors only.
‡ Follow local electrical codes.
(1) Process the end of the connecting cable for the indoor side.
(2) TDNH RfI WKH &DEOH +ROGHU IURP WKH EDFNVLGH RI WKH LQGRRU XQLW
(3) TDNH Rff the Connection Holder from the Wire Conduit and attach the Con-
QHFWLRQ KROGHU WR &DEOH +ROGHU ZLWK /RFN 1XW )LJ
 0DNH WKH FRQQHFWLQJ FDEOH JHW WKURXJK WKH &DEOH KROGHr.
(5) Attach the Cable Holder and Connection Holder to Cabinet with screw 5HIHU
to "ATTACH THE CABLE HOLDER AND CONNECTION HOLDER". (Fig.3
and Fig.4)
(6) ,QVHUW WKH FRQQHFWLQJ FDEOH LQWR WKH XQLW IURP EDFNVLGH
(7) Open the Open Panel.
(8) Connect the Connecting Cable to Terminal Board. (Fig.1)
(9) Fix the Cacle cover with the screw.
(10) Tighten the Connection Holder to Wire Conduit.
(11) Close the Open Panel.
Cautions:
‡ Be sure to put the cable leads deep into the terminal board and tighten up the
‡ Be very careful not to confuse the terminal connections. Wrong cabling may
damage the internal control circuit.
‡ %H VXUH WR FRQQHFW WKH FDEOH WR PDWFK WKH PDUNLQJV RQ WKH LQGRRU XQLW's termi-
nal board and those of the outdoor unit.
‡ )LUPO\ WLJKWHQ WKH ORFN QXW RI ZLUH FRQGXLW After tightening, pull the wire conduit
8QLW VL]H  
E
E
I
H
F
*
5.4 (137)
3.2 (80)
F
I
1 02817,1* 3/ATE
2 /21* 6&5(:
Length unit: in (mm)
&DELQHW VL]H  
E
D
J
D
C
A
B
3.2 (80)
Top of connecting
A
pipes
Center of wall hole
(8 mm) 0.3 in
8 Cable cover
5 Short screw
Power supply
208/230 V AC,
1phase 2 wires.
+]
*URXQG
5 – 2
5.4
(137)
J
Making a piping hole
(1) Drill a piping hole with concrete drill or
a hole saw with a 0.2inch (5mm) down
ward slant to the outside.
the diameter is 2.8inch (70mm).
(2) Set the sleeve and caps.
Wall
Outdoor
Indoor
Cut with a saw.
Cap
0.2 in (5 mm)
Sleeve
(Downward to
outdoor)
2.4 inch (60 mm)
2 inch (50 mm)
0.3 in (8 mm)
Earth Wire
Cable Holder
Connection Holder
(For Wire Conduit)
Terminal Board
L1
L2
2
Earth Wire
Cable Clump
(AY-XPC15PU, AY-XPC18PU,
AY-XP24PU)
Connecting Cable
Disconnect
287'225 81,7
switch
Terminal board 2
Fig.1
,1'225 81,7