GENERAL VENTING REQUIREMENTS AND
VENT PIPE SIZING AND MAXIMUM VENT LENGTHS (cont.)
(-)96VA0401317MSA
& (-)(-)96MDV040B30A
(-)96VA0601317MSA
& (-)(-)96MDV060B30A
(-)96VA0701317MSA
& (-)(-)96MDV070B30A
(-)96VA0851521MSA
& (-)(-)96MDV085C50A
(-)96VA1001521MSA
& (-)(-)96MDV100C50A
(-)96VA1151524MSA
& (-)(-)96MDV115D50A
* This is the recommended maximum number of long sweep elbows for either 2 or 3 inch pipe. Combinations
of long sweep 90s, standard 90s, or 45s may be used, but the manufacturer recommends the use of long
sweep 90s whenever possible because the use of the maximum number of standard 90 and 45 elbows
only may result in nuisance furnace outages due to individual installation specifics.
Exceeding the recommended maximum number of elbows may cause nuisance operation of the pressure switch.
GUIDELINES
49